4.4.3 Programmable Analog Outputs
There are 2 programmable analog outputs (see Figure 16). Analog Output 1 (program item 930) is
located on the front of the EPC typically used as a test point for debugging. Analog Output 2
(program item 933) is located on terminals 7 and 8 typically connected to an analog input of a
PLC.
Figure 16: Analog Outputs
The test point can easily be monitored externally. The signals for the programmable outputs are
selected in the Analog IO Configuration Form. Available Diagnostic signals are shown in Table
15.
Selection
Diagnostic
0
Output Disabled
1
Analog Input 1
2
Analog Input 2
3
Analog Input 3
4
Analog Input 4 (LVDT)
5
Current Feedback Signal
6
LVDT sine wave excitation signal
7
+12VDC Supply
8
-12VDC Supply
9
Servo Driver Output
10
Command to Pump Controller (Output of Active Function Program)
11
Ramp
Table 15: Diagnostic Signals