EPC
SERVO AMPLIFIER MODULE
Part Number L723888-3xx
ELECTRONIC
Telephone: (231) 929-1660
Oilgear
Fax:
(231) 929-7879
1424 International Dr
Issued May 31, 2018
Web Site:
www.oilgear.com
Traverse City, MI USA 4 9 6 8 6
Bulletin 836260F
10
4.1.3 Program Block Configuration (21x)
Program Item Range
Description
210
0 to 12
Program Selection for Program Block 1
0:
No Program used for Block 1
(refer to Section 4.3.2.1)
1-12:
Program 1 to 12 used for Block 1
211
0 to 12
Program Selection for Program Block 2
0:
No Program used for Block 2
(refer to Section 4.3.2.1)
1 to 12:
Program 1 to 12 used for Block 2
Table 3: Program Block Configuration
The program block configuration parameters are used in conjunction with the module operating
modes to assign pre-defined programs to the two (2) program blocks.
Dynamic Operating Modes: These modes are referred to as “dynamic” because the digital input
selects which Program Block is active. If the digital input is low (<5 VDC), Program Block 1 is
made active and the program defined in menu 210 is used. If the digital input is high (> 5VDC),
Program Block 2 is made active and the program defined in menu 211 is used (see Example).
Static Operating Modes: These modes are referred to as “static” because Program Block 1 is
always active and menu 210 defines the active function program. Menu 211 has no function in
operating mode 2. The static operating modes also free the digital input to be used for a function
other than program selection.