制御盤内で除湿されたドレン水は、以下の方法で蒸発されます。

 

     

 

制御盤内で除湿され発生したドレン水は、ドレン水蒸発皿に溜まります。

 

ドレン水蒸発皿内部には、蒸発コイルがあり、温められたドレン水が上部を通過する

 

盤外空気により気化し、外部へ蒸発します。一方、蒸発コイルが冷たいドレン水により

 

冷却されるため、冷凍回路の放熱効率が上がります。

 

Condensate water generated inside an enclosure will evaporates as described below.   

Water resulted from dehumidification that took place in an enclosure will pool   

in the Evaporation pan. Evaporation coil is equipped in the pan to heat up the water.   

Heated water will vaporize by the external air that passes above the pan and goes out.   

Meanwhile, the evaporation coil is cooled by cold drain water,   

and thus heat radiation rate increases. 

     

 

ドレン水蒸発皿で蒸発されないドレン水は、ドレン水蒸発フィンへ流れていきます。

 

高温のドレン水蒸発フィンにより、さらに温められたドレン水は、フィンを通過する

 

盤外空気により気化し、外部へ蒸発します。この蒸発の際に、ドレン水が周りから

 

熱(気化熱)を奪うため、冷凍回路の放熱効率が上がります。

 

        

Residue water in the Evaporation pan will flow to the Evaporation fin.   

By the high-temperature Evaporation fin and the external air that passes through   

the fin, the water vaporizes into the atmosphere. Meanwhile, such evaporation takes   

heat away from the surroundings and it brings about higher heat radiation rate. 

 

     

③ ドレン水蒸発フィンで蒸発されないドレン水は、ドレン水蒸発シートへ給水されます。

 

コンプレッサの熱とコンデンサの熱で温度上昇した盤外空気により気化し、外部へ蒸発します。

 

       

As the final step, the Evaporation sheet absorbs the water not evaporated   

in the Evaporation fin to evaporate it by the hot external air heated   

by the compressor and the capacitor.

 

     

④ 盤内・盤外温湿度:35℃、

85

RH

以下で発生するドレン水は

3

つの蒸発機構により

 

蒸発されますが、ノンドレン機能の仕様範囲外で発生するドレン水は、ドレンパイプより

 

盤外へ排水される構造となっています。

 

       

This product is designed to process condensate by the above 3-step evaporation   

mechanism on condition that both internal and external temperature   

and humidity conditions are under 35 deg. C, 85% RH. Condensate water produced   

outside the above range is to be discharged through the drain pipe.

 

 

 

 

 

3.制御盤への取付け方法

  

Mounting

 

3-1

 

取付けに関するご注意

 

Caution

 

危険

  Danger

 

 

クーラを制御盤へ取付けるときは、感電防止のため制御盤自体への電源供給を

 

停止させてください。

 

For prevention of electrical shock, power supply to the control panel should be 

disconnected before installation work.

 

 
 
 
 
 

注意

  Caution

 

 

クーラの設置には、付属品以外のものは使用しないでください。

 

 

→故障やケガの原因になります。

 

For installation, do not use any parts other than originally supplied ones.   

Failure to this may result in injury or breakdown of the cooling unit.

 

取付穴

(M6)

に直接回転力が加わるような使い方はしないでください。

 

 

→取付穴にはカシメ袋ナットを採用しているため空転する恐れがあります。

 

In case screws are used for installation instead of the original bolts, put a plate 

between the screw and the cap nut so as the direct torque not to be transmitted. 

Or, the cap nut may cause slipping.

 

Summary of Contents for COOL CABI OCA-H1300BCD

Page 1: ...struction Manual Lateral Mounting Type Condensate free Type OCA H350BCD OCA H700BCD OCA H1300BCD OCA H2300BCD Please read this brochure carefully before use and keep at hand for future reference Cauti...

Page 2: ...2 Contents Safety Precautions Part names and evaporation mechanism Mounting Wiring Operation Alarm Safeguard Maintenance Specifications Warranty Waste disposal...

Page 3: ...r remove the front cover of the unit during operation Do not put your fingers or foreign matters into rotating part of the fan Always disconnect power and wait until the fans stop completely before st...

Page 4: ...ismount or relocate the cooling unit or the enclosure itself after operating the cooling unit for some time remove water in the Evaporation pan and the Water pan in the cooling unit interior using a d...

Page 5: ...hock and vibrationdduring operation drain water inside of it may leak out Evaporation pan Evaporation fin Evaporation sheet External fan Compressor Outside air Evaporation Capacitor Drain pipe Water p...

Page 6: ...step the Evaporation sheet absorbs the water not evaporated in the Evaporation fin to evaporate it by the hot external air heated by the compressor and the capacitor 35 85 RH 3 This product is designe...

Page 7: ...ove may result in poor cooling performance or condensation The supply voltage must be as specified on the rating plate of the unit Electrical connection should be made via appropriate circuit breakers...

Page 8: ...is found during cooling operation improve the environment by attaching rectifying plates or installing agitation fans as necessary Mounting procedure External mounting P 9 Process the mounting surfac...

Page 9: ...s Please lift up evenly using eyebolts whenever lifting up a cooling unit Lifting up one side only may result in breakdown or damage of the product Cutouts for External Mounting View from outside the...

Page 10: ...10 OCA H1300BCD A200 OCA H2300BCD A200 Arrangement of packing Ex OCA H350BCD OCA H1300BCD OCA H350BCD A200 OCA H1300BCD A200 Packing shaded area Packing shaded area...

Page 11: ...temperature humidity range i e temperatures not exceeding 35 deg C and humidity not exceeding 85 RH for both ambient and enclosure interior When the evaporation fin or the evaporation sheet is dirty...

Page 12: ...poration pan and water pan using a syringe or a wiping cloth Otherwise such water may spill over from these pans Remove the front panel The downside of the panel is fixed with a screw and the upside i...

Page 13: ...ding Wiring procedure Applicable wire range AWG24 12 0 2 2 5mm2 6 7mm Strip the wire by 6 to 7 mm Push down the Push button with a flathead screwdriver Insert a wire into the port Release the screwdri...

Page 14: ...ssor External fan 1pc Sensor Terminal board Terminal board OCA H350BCD H1300BCD OCA H700BCD Ex OCA H700BCD Internal fan 2pc Compressor External fan 4pc Control board Terminal board Sensor Terminal boa...

Page 15: ...er supply or with the start of cooling operation COOLCABI is subject to starting current for approx one second Therefore the selection of an earth leakage breaker should be made so as to assure stable...

Page 16: ...equent on off occurs Never put your fingers into the unit or uncover the unit during operation Failure to this may be a cause of injury Never operate COOLCABI leaving the control panel door open Failu...

Page 17: ...ration After a lapse of the time set by parameter the unit will return to normal operation mode Note Factory setting for compulsory operation is 30 seconds Parameter setting Normally there is no need...

Page 18: ...aintenance works in a timely manner 0 This function is ineffective 1 99 1 means 100 hours Notification period can be set between 100 to 9900 hours Time measurement in the control board is made on an h...

Page 19: ...ugh the display shows E4 AS 0 0 3 0 1 2 3 P21 23 Setting assignment of alarm output terminals AS Initial setting 0 Setting range 0 3 Alarm output terminals output once an alarm is detected This is to...

Page 20: ...for external fan and compressor t2 Initial setting 3 Setting range 3 10 minutes This is to set the time period for restarting the compressor after shutdown For prevention of frequent ON OFF of the co...

Page 21: ...ration and alarm occurrence AS 1 The state of alarm output terminals changes responding to the state of cooling operation and alarm occurrence AS 2 Monitoring of need for power shutdown and restoratio...

Page 22: ...F OPEN Cooling operation is stopped OPEN 2 Contact changes over by the state of alarm which requires power shutdown and restoration E5 SE Alarm E5 or SE ON CLOSE Contact changes over by the state of a...

Page 23: ...CLOSE Cooling operation is stopped OPEN 2 Contact changes over by the state of alarm which requires power shutdown and restoration E5 SE Alarm E5 or SE ON OPEN Contact changes over by the state of al...

Page 24: ...the high temperature alarm setting when power is turned on the alarm lamp lights by the setting of AS and Ao according to the assignment table of alarm output terminals described in page 22 and 23 3 C...

Page 25: ...has stopped The internal fan runs continuously when the internal temperature exceeds the differential temperature ly when the internal temperature exceeds the differential temperature Note 5 There is...

Page 26: ...ressor is forcibly stopped by the set time period In case the heat value inside the enclosure is large the internal temperature can even exceed the high temp alarm temperature value For prevention of...

Page 27: ...the alarm output terminals will break and make contact as set in AS and Ao See the assignment table of alarm output terminals in page 22 and 23 The display shows the current internal temperature and E...

Page 28: ...sconnection of the internal temperature sensor for some reasons The alarm will light and the alarm output terminals will break and make contact as set in AS and Ao See the assignment table of alarm ou...

Page 29: ...no need of maintenance for the circuit The durability of COOLCABI is generally 30 000 operating hours provided that its filter is kept clean Depending on the environmental condition at the site of use...

Page 30: ...OCA H700BCD A200 Replacement of internal fan Ex OCA H700BCD A200 In the event of a fan failure go through the following steps to replace the fan Remove the 4 screws and detach the fan mounting plate...

Page 31: ...ews of the Maintenance panel Blow off dirt of the Evaporation fin by means of compressed air or other means Slide the anchorage upward to remove and take out the Evaporation sheet Clean the Evaporatio...

Page 32: ...one of higher capacity Ambient temperature is too high 50 This unit is unusable under a circumstance where the ambient temperature may exceed 50 Internal temperature is too high 45 This product canno...

Page 33: ...lay shows SE Memory breakage Contact the supplier Drain hose discharges water The cooling unit is used outside the specified working conditions Use within the specified range Incoming air volume has d...

Page 34: ...70W 470 500W 630 690W Compressor motor output 100W 275W 375W A Noise Characteristic A 62dB 65dB 65dB Refrigerant Type Designation HFO R1234yf Amount 150g 210g 430g 4 GWP 1 Outer dimensions W H D mm 30...

Page 35: ...stic A 69dB Refrigerant Type Designation HFO R1234yf Amount 1000g 4 GWP 1 Outer dimensions W H D mm 450 1150 250 Weight approx 52 0kg 1 35 Nominal value when temperatures both inside and outside the c...

Page 36: ...ssipation Detection of temperature sensor disconnection External output 1a 240V 1 5A 2 COMMON Alarm output 1a 240V 1 5Ax2 Output Common Vibration resistance 10 55Hz 0 15mm 10 Vibration frequency 10 55...

Page 37: ...A H700BCD OCA H1300BCD OCA H2300BCD COOLCABI 1 Fixing bolt M6 35 4 M6 35 6 M8 35 6 Washer M6 4 M6 6 M8 6 Spring washer M6 4 M6 6 M8 6 Nut M6 4 M6 6 M8 6 Packing 1 1 roll Drain hose 2m Terminal board 1...

Page 38: ...ration Evaporation sheet Terminal board 12 Drain pipe Outer dia 12 12 Drain pipe Outer dia 12 Bottom view Front view Right side view Rear view 4 M6 14 4 M6 Depth 14mm For fixing bolt Left side view Wa...

Page 39: ...e Cool air Operation Evaporation sheet Terminal board Top view External air inlet filter White 2 M8 13 2 M8 Depth 13mm For eyebolt Left side view Rear view Front view Right side view Bottom view Top v...

Page 40: ...r than air they have a risk to stay on the floor surface when they are released to air in a place with poor ventilation To release a refrigerant select a place free from fire having good ventilation a...

Reviews: