background image

Effective 11/2010

 

 

19

 

Internal Components Description

 

Power Distribution Panel 

The terminal board distributes electrical power to the different components of 

the system.   

Inlet Air Filter  

The air filter keeps dust and dirt from entering the compressor and needs 

to be changed twice a year in normal environments to maintain the unit

‟s 

performance.  It should be changed more often in dirty, oily areas.   

Four (4) times a year is recommended.  

 

PLC 

The PLC (Programmable Logic Controller) processes inputs and outputs to and 

from system components, and communicates with the touch screen.  This is the 

brain of the machine.  

 

Back Pressure Regulator 

Gauge 

This gauge controls the balance between oxygen flow and oxygen purity.  

Initial setting is between 

45

 

psi (3.1 bar)

 and 

50 psi (3.4 bar)

.  A higher back 

pressure will increase purity but decrease storage tank pressure.  A lower  back 

pressure will increase storage tank pressure but decrease purity.  This regulator 

will adjust the storage pressure and oxygen purity. 

Air Storage Tank 

Air from the air compressors is stored in this tank before going through the 

sieve bed sets on the side of the machine.  Normally this tank pressure holds 

between 

23 psi (1.6 bar)

 and 

26 psi (1.8 bar)

.   

Air Compressor 

The air compressors supply the feed air for the sieve beds.  They are held in 

place by four bolted rubber mounts and can be easily replaced when necessary.  

They should work as designed for a minimum of 10,000 hours and will last 

20,000 hours in many cases.   

Air Pressure Transducer 

The transducer gives a variable output current to the PLC at different pressures.  

The PLC then communicates this signal to a virtual gauge in the touch screen.   

Oxygen Generators 

These generators contain the molecular sieve that performs the air separation 

process.  Exposing the internal sieve material to the atmosphere will cause 

contamination.  However, if the sieve becomes contaminated the beds can be 

easily replaced.   

Low Oxygen Pressure 

Transducer 

The transducer gives a variable output current to the PLC at different pressures.  

The PLC then communicates this signal to a virtual gauge in the touch screen.   

Oxygen Purity Sensor  

The oxygen sensor gives a variable output current to the PLC at different levels 

of oxygen purity.  The PLC then communicates this signal to a virtual gauge in 

the touch screen.  See 

Appendix Page IV

 for details on how to make an 

adjustment to this sensor.   

Summary of Contents for MOGS - 100

Page 1: ...ion and Maintenance Manual Oxygen Generating Systems Intl OGSI 814 Wurlitzer Drive North Tonawanda New York 14120 USA Tel 716 564 5165 Toll Free 800 414 6474 Fax 716 564 5173 E mail ogsimail ogsi com...

Page 2: ......

Page 3: ...1 Specifications 22 Safety Precautions 23 Pre Installation 24 Required Operating Conditions 25 Set up and Installation 26 Operating Instructions 27 Troubleshooting Guide 28 Touch Screen Overview 30 Ma...

Page 4: ...2010 OGSI All rights reserved OGSI is a registered trademark This publication may not be reproduced in part or whole without written permission of OGSI...

Page 5: ...Password to Access Touch Screen 647401 Please take appropriate measures to keep this password secure and prevent unauthorized access...

Page 6: ......

Page 7: ...n our warranty policy features functions applications proper set up and installation operation and maintenance of our products The following symbols are used throughout the manual Information Do not u...

Page 8: ...ned in the future the original crate is the best way to ship it back to the manufacturer Claims of damage due to freight handling can only be filed by you the consignee as OGSI shipping terms are Free...

Page 9: ...ucts to OGSI Once the Products are repaired OGSI will ship the Products back to the original user and cover all costs incurred in shipping 2 OGSI shall repair or replace the Products excluding filter...

Page 10: ...roducts by anyone other than an authorized representative of OGSI The authorized service representative must obtain prior approval from OGSI s Service Manager before performing any warranty work c Ext...

Page 11: ...orrected by tightening a valve gland or packing nut the valve should be closed and a tag attached stating that the cylinder is not serviceable Remove the cylinder outdoors to a well ventilated or open...

Page 12: ...e permitted in the area where the generator is located All oxygen connections and hoses should be kept clean and free of grease oil and other combustible materials Valves controlling oxygen flow shoul...

Page 13: ...th a UL listed electrical panel It has a sound attenuating enclosure with slam action latches and lift off hinges Economical The MOGS 100 unit reduces oxygen supply costs by 80 or more in most cases I...

Page 14: ...e 11 2010 8 Applications The MOGS 100 can be used in various applications A few examples are given below EMS Emergency Medical Services Fire Departments Hospitals and Clinics Veterinary Centers Nursin...

Page 15: ...ve The process is described below This air separation process is reliable and virtually maintenance free The molecular sieve will last indefinitely as long as it does not become contaminated with wate...

Page 16: ...Effective 11 2010 10 External Components Front View 1 Control Panel 2 Fill Blast Containment Chamber 3 Side Access Door 4 Front Access Door 5 Frame Inlet Air Filter Underside...

Page 17: ...Effective 11 2010 11 Rear View 1 Upper Auxiliary Oxygen Port 70 90 psi 2 Lower Auxiliary Oxygen Port 1900 2200 psi 3 Reserve Oxygen Cylinder Bank 4 Power Cord...

Page 18: ...Effective 11 2010 12 MOGS 100 with Auxiliary Manifold and Cylinders 1 Auxiliary Cylinder Filling Manifold Shown with Copper Pigtails Optional 2 Extra Reserve Cylinders Optional...

Page 19: ...Gauge 2 Reserve Bank Valve 3 Reserve Bank Pressure Gauge 4 Fill Chamber Pressure Regulator 5 Regulated Pressure to Containment Chamber 6 Emergency Stop Button 7 Valve Fill Chamber 1 8 Gauge Fill Chamb...

Page 20: ...compressor inside the MOGS and delivering oxygen at 70 psi 4 8 bar directly to a clinic hospital or other application In order to do this the oxygen compressor inside the machine must be switched OFF...

Page 21: ...inders loaded in the fill blast containment chamber Emergency Stop Button This button allows the oxygen generator power to be instantly shut off in the event of an emergency This button should not be...

Page 22: ...on Panel 2 Inlet Air Filters 3 Programmable Logic Controller PLC 4 Back Pressure Regulator Gauge 5 Air Storage Tank 6 Air Compressors Bank 5 7 Air Pressure Transducer 8 Oxygen Generator Bank 5 9 Low O...

Page 23: ...Effective 11 2010 17 Rear View 1 Heat Exchanger 2 Compressed Air Filter 3 Back Pressure Regulator 4 Oxygen Storage Tank 5 Refrigerant Dryer...

Page 24: ...Effective 11 2010 18 Fill Blast Containment Chamber 1 Fill Whip 1 2 Fill Chamber 1 3 Fill Whip 2 4 Fill Chamber 2...

Page 25: ...ve bed sets on the side of the machine Normally this tank pressure holds between 23 psi 1 6 bar and 26 psi 1 8 bar Air Compressor The air compressors supply the feed air for the sieve beds They are he...

Page 26: ...o represent oxygen as opposed to the grey color of the air tank The generator will run according to the pressure in this tank ON at 70 psi 4 8 bar OFF at 90 psi 6 2 bar With the oxygen at this pressur...

Page 27: ...ve in that bed is saturated with nitrogen When this occurs the feed air flow is directed to the other bed which continues the production process While the second bed is producing oxygen the first bed...

Page 28: ...00 ppm CO Output 10 ppm Oxygen Dew Point 100 F 73 C Response Time Approximately 5 minutes to attain maximum purity after initial start up or extended shut down Physical Air Inlet Filtration Level 0 3...

Page 29: ...hould become the designated operators of the MOGS 100 unit within your facility In critical applications it is important to have a backup supply of oxygen since the generator does not come with any re...

Page 30: ...d a nitrogen build up could be dangerous to people entering the room If the generator is placed in a small closet the air in that closet will become enriched with nitrogen As the oxygen generator cont...

Page 31: ...entrations of hydrocarbons especially carbon monoxide Humid oily areas should be avoided as installation sites as much as possible Ambient Air Temperature The machine is designed for use over a temper...

Page 32: ...ng a password and selecting a language start the machine by pressing both the Operating Mode AUTOMATIC and then the ON OFF buttons Listen for the sound of the compressors and cooling fan to start runn...

Page 33: ...ing ensure that the air compressor indicator toggles from red to green The oxygen booster compressor should toggle from red to green after the oxygen compressor is activated and that will occur when t...

Page 34: ...greater than the set Low point Check the ALARM screen for any faults A WARNING ACTIVE sign will appear at the bottom of each screen if a fault has occurred System shuts down inadvertently WARNING ACT...

Page 35: ...any leaks The machine has run for 30 minutes and purity has not yet been reached This may be a result of a leak in the system Use a leak testing solution to locate and repair any leaks Oxygen purity h...

Page 36: ...n the touch screen Language selection Password protection Energize de energize the machine Monitor the operating condition of valves and compressors Monitor all system pressures and oxygen purity Hour...

Page 37: ...Effective 11 2010 31 Language Screen The language screen enables the user to choose the language English French or Spanish After choosing a language select MAIN MENU...

Page 38: ...r to enter the password supplied by the manufacturer Select PASSWORD AREA Enter the password using the numeric keypad displayed on the screen Select ENTER The password will be verified and the screen...

Page 39: ...een allows the user to navigate through the program from screen to screen and it will get you where you need to go inside the program Note A notification will appear at the top of the screen only if t...

Page 40: ...the mode of operation Operating Mode This feature allows the selection of either MANUAL or AUTOMATIC modes The AUTOMATIC mode will initiate machine operation when the ON OFF button is in the ON positi...

Page 41: ...hey are energized Oxygen Compressor This feature monitors the operational condition of the oxygen booster compressor When the oxygen compressor is de energized the feature will display STANDBY and wil...

Page 42: ...e TIMER SETUP above Hours Meter This meter displays the accumulated operating time of the system This meter will increment only while the system status is CYCLING and will reset to zero 0 after 10 000...

Page 43: ...pressure after entering the oxygen generator sieve beds typically in a range of 4 10 psi 0 3 0 7 bar Air Tank Pressure This feature displays the pressure associated with the air storage pressure tank...

Page 44: ...displayed on the GAUGE screen for up to the previous 24 hour period Note that the machine only has a 24 hour memory when it is ON so after 24 hours it will start deleting or writing over previous hist...

Page 45: ...plays warnings when any of the following faults occur 30 Minute Warning Air compressors have been running 30 minutes and the purity has not yet reached an acceptable level This could occur for a numbe...

Page 46: ...molecular sieve inside one or more of the oxygen generators Warning Contact OGSI if this warning occurs These warnings must be cleared after following the instructions on the displayed warning indica...

Page 47: ...ber of the Machine and its Serial Number are displayed along with the Date of Completion The software versions for both the Programmable Controller and Touch Screen are also shown During the course of...

Page 48: ...ON OFF button This will only activate that set of sieve beds Then after 15 minutes of running you will see on the Oxygen Purity Gauge if that sieve bed set is not running properly making at least 90...

Page 49: ...nglish or Spanish Select DISPLAY TEST The screen will display all the colors continuously allowing the user to see if a color is not displayed correctly Select EXIT at any time to go back to the previ...

Page 50: ...Effective 11 2010 44 MOGS 100 Filling Manifold Design Installation Optional...

Page 51: ...nd installing a cylinder filling manifold it is necessary to ensure that the threads on all NPT connections and all stainless steel on stainless steel connections are lubricated by Teflon tape or a si...

Page 52: ...s depending on the previous certification The date of last certification is stamped on the collar of the cylinder month and year only If a star symbol is stamped next to the date re certification is n...

Page 53: ...frame of the machine From this port an auxiliary high pressure manifold can be connected increasing the size of the reserve bank by 3 4 etc additional cylinders These additional high pressure reserve...

Page 54: ...e is present The use of safety glasses and hearing protection is required Slowly disconnect the steel whip from the cylinder valve using 11 8 wrench Be aware of the venting of oxygen under high pressu...

Page 55: ...t of a spares kit Cabinet The cabinet should be occasionally washed down with a sponge or clean rag and some soapy water Avoid the use of ammonia or other strong chemical based cleaning solvents The i...

Page 56: ...oil less compressor that should last two 2 to four 4 years under normal conditions Low Oxygen Tank pressure less than 60 psi or 4 1 bar will be an indicator that this booster needs to be replaced Rep...

Page 57: ...irect number By Telephone Outside the United States Your local International Access Code usually 0 or 00 followed by The Country Code for the U S which is 1 followed by Our Area Code and Number 716 56...

Page 58: ......

Page 59: ...Appendix...

Page 60: ......

Page 61: ...1 100 psi Pressure Transducer medium oxygen pressure 1910001 100 1 50 psi Pressure Transducer low oxygen pressure 1910001 050 1 Oxygen Booster Pump 212000T 220 1 Oxygen Purity Sensor 3110003 008 1 Re...

Page 62: ...Care needs to be taken in the cleaning and handling of components used in oxygen service to prevent any contamination related failure While the CGA G 4 1 2009 standard makes allowance for cleaning pa...

Page 63: ...oved from the washer once the drying cycle is complete Inspection Upon completion of the final cleaning cycle all parts should be removed from the parts washing machine and inspected for any residual...

Page 64: ...brate the zero point of the sensor Normal air has 20 9 oxygen in it and air can be used as a zero gas for sensor calibration Procedure Disconnect the oxygen sample line feeding the sensor and let the...

Page 65: ...4 4 3 OG 175 NR 25 18 12 5 11 10 8 6 5 5 4 OG 250 NR 30 22 5 15 13 11 9 7 5 7 6 5 OG 375 NR NR 30 27 22 5 18 15 13 11 8 7 OG 500 NR NR NR 30 27 22 5 18 15 13 11 8 OG 650 NR NR NR NR 30 27 22 5 18 15 1...

Page 66: ...kWh Kilowatt hour ft3 Cubic Feet VAC Volts Alternating Current Hz Hertz SCFH Standard Cubic Foot per Hour SCFM Standard Cubic Foot per Minute LPM Liter Per Minute 1 bar 1 45 x 101 psi dBA Decibel A sc...

Page 67: ...Effective 11 2010 VII Maintenance Log Date Part Reason for Maintenance Authorized Service Technician Signature...

Reviews: