Multi-functional DC inverter air/water heat pump
GB
Changing the
operating mode
4.4.2.4
Flow t
emper
at
ur
e hea
ting in °C
Setting operating times
4.4.2.5
Auto temp. is an operating mode for automatic temperature setting of the heat pump,
subject to the ambient temperature according to the following auto-heat curve.
A. Whether the Auto Temp. operating mode is valid or not, depends on parameter P19.
0-setting means the mode is not valid, 1 means valid.
B. Shifting the automatic heating curve is defi ned by parameter P09. A positive value
means rising, a negative value means dropping (-10 °C ~10 °C).
C. The highest temperature of the automatic heating curve is defi ned by parameter P08,
from 30 ~50, standard 45. If the parameter is 45, the highest AU target temperature is
45 °C.
P08 = 50 °C MAX
P08 = 45 °C STANDARD
P09
+10 °C
P08 = 35 °C MIN
P09
-10 °C
Outside temperature in °C
P09
+10 °C
P08 = 50 °C MAX.
P08 = 45 °C STANDARD
P08 = 35 °C MIN.
P09
-10 °C
Click timer button
to set the operating time for the heat pump and C3 pump.