9
ACCESSORIES
EVAPORATOR RETURN AIR PLENUM
Evaporator return air plenums are available for installations where it is required to duct
air to the inlet of the evaporator. The evaporator return air plenums allow the user to
connect round duct (flexible or rigid) to the return air intake to reduce air noise and
increase the number of options for solving difficult cooling problems. The plenum
attaches to the front of the unit, replacing the return air grille. Refer to the table below
for configuration and application information
DEP-10
for PWC12
transitions the return air opening to a 10-inch round duct.
2DEP-12
for PWC18 and PWC24
transitions the return opening to a 12-inch round duct.
DEP-16
for PWC36 and PWC60
transitions the return opening to a 16-inch round duct.
NOTE
—
When a DEP/2DEP is installed, it is recommended to set the evaporator blower
speed to high, to avoid evaporator coil freeze-up.
Plenum Kit
Duct/
Flange
PWC12
PWC18
PWC24
PWC36
PWC60
FILTERS
DEP-10
10 inch
✓
(1) 10”x 20”x 1”
2DEP-12
12 inch
✓
✓
(1) 16”x 24”x 1”
DEP-16
16 inch
✓
✓
(1) 12”x 30”x 1”
(1) 10”x 30”x 1”
Maximum
Equivalent
Feet
25
50
60
70
80
Est. External
Static
Pressure
(.20)
(.25)
(.25)
(.25)
(.50)
FILTER(S)
EVAPORATOR RETURN
AIR PLENUM
Summary of Contents for PWC Series
Page 23: ...21 PIPING SCHEMATIC...
Page 24: ...22 WIRING SCHEMATIC FOR PWC1211 PWC1811 PWC2412 and PWC3612...
Page 25: ...23 WIRING SCHEMATIC FOR PWC6012 07182016...
Page 26: ...THREE PHASE MONITOR 24...
Page 27: ...25 WIRING SCHEMATIC FOR PWC3632...
Page 28: ...26 WIRING SCHEMATIC FOR PWC6032...
Page 29: ...27 WIRING SCHEMATIC FOR PWC3634 and PWC6034...
Page 31: ...TECH NOTES 29...