WATER VALVE ADJUSTMENT
Each OCEANAIRE WATER-COOLED unit is equipped with an automatic water
regulating valve to control the condenser water flow rate. The water valve will open
when the unit is in the cooling mode and adjust the gallon per minute flow rate
based on the entering water temperature (EWT).
The water valve operates independently from the water system, and regulates flow
based on the systems refrigerant head pressure.
Under certain conditions, entering water temperatures can cause the valve to
rapidly open and close, causing a “harmonic” pitch in the water supply line. In these
cases, it is recommended that the water valve be adjusted.
1.
Disconnect the unit power.
2. Remove water valve cover plate or back panel (depending on model) to
locate the water valve.
3. At the top of the valve, there is a square shaped adjustment screw. Using a
standard service wrench or flat blade screwdriver, adjust the valve using
quarter turns, allowing the unit to operate approximately 5 minutes after
each new setting.
•
CLOCKWISE (CW) opens the valve, which lowers HIGH side pressure, and
lowers the valve’s set point to open.
•
COUNTER-CLOCKWISE (CCW) closes the valve, which raises HIGH side
pressure, and raises the valve’s set point to open.
4. Re-install cover plate (or back panel) when finished.
Water Valve
Adjustment
Screw
Water Valve
Cover Plate
Summary of Contents for PWC Series
Page 23: ...21 PIPING SCHEMATIC...
Page 24: ...22 WIRING SCHEMATIC FOR PWC1211 PWC1811 PWC2412 and PWC3612...
Page 25: ...23 WIRING SCHEMATIC FOR PWC6012 07182016...
Page 26: ...THREE PHASE MONITOR 24...
Page 27: ...25 WIRING SCHEMATIC FOR PWC3632...
Page 28: ...26 WIRING SCHEMATIC FOR PWC6032...
Page 29: ...27 WIRING SCHEMATIC FOR PWC3634 and PWC6034...
Page 31: ...TECH NOTES 29...