![OBO Bettermann EI30 Mounting Instructions Download Page 44](http://html1.mh-extra.com/html/obo-bettermann/ei30/ei30_mounting-instructions_3169658044.webp)
44 | EN
OBO Bettermann
Mounting PYROLINE® Con S PLC with a support system
8 6
Mounting fittings
The PYROLINE
®
Con S PLC product version offers prefabricated fittings
for various cable routing requirements:
– 90° bend to run cables around a corner
– T piece to branch a cable off
– Vertical bend, rising/falling, in order to route the cable upwards/down-
wards in a slanting manner
Fittings must be supported by additional brackets. The cables must be
routed before the duct cover is mounted.
100 mm
100 mm
Fig 37:
Support on fittings
1. Draw the drill holes for wall brackets, suspended support or threaded
rods, so that the brackets have a maximum spacing of 100 mm to the
joints of the fitting.
2. Draw on the drill holes and mount the brackets, suspended support or
threaded rods (see chapter “8.1 Mounting the wall bracket” on page
38, “8.2 Mounting the suspended support and bracket” on page
39 or “8.3 Mounting the threaded rod and support rail” on page
40).
3. Apply sealing strips to the joints of the fitting if there is no sealing strip
on the joining cable troughs yet.