12 | EN
OBO Bettermann
Selecting the fire protection duct
5 Selecting the fire protection duct
Depending on the required classification, fire protection ducts with differ-
ent wall thicknesses and mounting systems are used.
5 1
Fire protection duct for direct wall/ceiling mounting
Direct wall and ceiling mounting is particularly appropriate when no
pipes need to be refitted, buildings refurbished or surface refinement is
required, in order to integrate the duct visually into the appearance of the
room. The duct covers are screwed to the duct trough.
Classification
Duct type
PYROLINE
®
Con D PLC
Internal
dimensions
h x w in mm
External
dimensions
h x w in mm
Weight/m in kg
without cable
assignment
EI30–EI60
PLCD D060810 80 x 100
125 x 160
10.0
EI30–EI60
PLCD D061220 120 x 200
165 x 260
15.7
EI90
PLCD D090810 80 x 100
140 x 180
13.7
EI90
PLCD D091220 120 x 200
180 x 280
21.0
Tab 3:
Fire protection ducts for direct wall/ceiling mounting for EI30–EI60 and EI90
classification
5 2
Fire protection duct for mounting with a support system
Mounting with a support system is particularly useful if obstacles such as
heating, ventilation or water pipes or joists must be refitted. The support
system can consist of
– wall supports,
– suspended supports with support brackets and threaded rods
– or threaded rods and support rails.
With wall supports, it is possible to compensate for larger unevenness-
es in walls or avoid vertical cables or pipelines. Support systems with a
suspended support and support bracket are easier to fill with cables. If
suspended with threaded rods, a smaller mounting area under the ceil-
ing is required. The selection of the support system is aligned to the local
conditions.
The duct covers are not screwed to the duct trough, thus allowing rapid
inspection and refilling.
Classification
Duct type
PYROLINE
®
Con S PLC
Internal
dimensions
h x w in mm
External
dimensions
h x w in mm
Weight/m in kg
without cable
assignment
EI30–EI60
PLCS D060810 80 x 100
140 x 160
13.7
EI30–EI60
PLCS D061220 120 x 200
180 x 260
19.9
EI90
PLCS D090810 80 x 100
180 x 200
24.6
EI90
PLCS D091220 120 x 200
220 x 300
37.8
Tab 4:
Fire protection ducts with support system for EI30–EI60 and EI90 classification