Mounting PYROLINE® Con D PLC on a wall/ceiling
K1
2
2
2
Fig 4:
Duct trough mounting
2. Place the first duct trough
K1
directly on the wall at the end of the
room.
3. Draw the drill holes.
4. Drill holes in the wall/ceiling according to the selected means of fas-
tening (dimensions at least M6), e.g. for the MMS-plus P 7.5x80 bolt
tie with Ø 6 mm.
5. Apply sealing strips
2
to the front side of the duct trough
K1
.
A
3 mm
2
B
3 mm
2
C
3 mm
Fig 5:
Wall mounting with separating brackets
A
,
ceiling mounting with separating
clamps
B
,
vertical mounting with cable fixing device
C
6. Mount the duct trough in conjunction with the separating bracket
A
/
separating clamp
B
/cable fixing device
C
and MMS bolt tie. During
mounting, compress sealing strips
2
to a maximum of 3 mm.
7. Attach the duct trough to the end of the duct trough
K1
and mount in
the manner described in points 3–6.
8. Shorten the last duct trough to the wall with a hand or coping saw,
removing 3 mm from the residual length for the necessary joints.
9. Apply sealing strips to both front ends of the last duct trough.