30 | EN
OBO Bettermann
Mounting PYROLINE® Con D PLC on a wall/ceiling
7 8
Mounting an end piece
1
1
2
Fig 23:
End piece mounting
The fire protection duct must be tightly closed to prevent fire from
spreading to the cables or smoke gases from escaping during a cable
fire. Open cable ends are closed off with an end piece suitable for the
fire protection duct.
1. Stick the sealing strip on the front side
1
of the mounted fire protec-
tion duct.
2. Mount the end piece in front of the end of the duct with at least 4
counter-sunk head screws
2
.