Mounting PYROLINE® Con D PLC on a wall/ceiling
Mounting version
C
– Uncut duct penetration, no wall connection collar
1
2
max. 2 cm
Fig 29:
Wall connection mounting version
C
1. Create a wall opening for the duct penetration.
Note!
Wall opening max. 2 cm > external duct dimensions.
2. Run the fire protection duct through the wall opening and mount it on
the wall
1
, see also “7.1 Mounting the duct trough” on page 15.
3. Close the ring gap around the duct with MIW-S mineral wool
2
.
4. Seal the mineral wool with non-combustible material, e.g. plaster.