background image

7

01. 09. 21. Document Number  671746

Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk

BPS V-AT

Installation Manual

6.0 MECHANICAL INSTALLATION

Installation must be completed by competent persons, in accordance 
with good industry practice and should conform to all governing and 
statutory bodies i.e. IEE, CIBSE, etc.

The unit should stand upright and level on the floor, foundation 
or supporting steelwork which should be rigid, flat and level and 
should be capable of supporting the weight of the unit including 
water or refrigerant in the coils. Nuaire takes no responsibility for the 
coordination of support.

6.1 Unit Location

To prevent possible reintroduction of contaminated air through the 
outside air intake, the unit should be located away from building flue 
stacks or exhaust ventilators.

Once assembled and in position, sufficient free space must be available 
adjacent to the unit for future inspection, maintenance, component 
service, repair and replacement and connection of services. It is 
recommended that at least the unit width (vertically arranged units) 
+ 100mm be allowed. A minimum of 600mm is required for regular 
maintenance.

Sufficient clearance for U-traps on condensate drain and overflow 
connections should also be considered by the purchaser.

6.2 Air Leakage

Loading, transportation, off loading and site positioning can cause 
the air handling unit structures to move, therefore panel seals will not 
always remain fully intact.

It is inevitable that in such cases, re-sealing of the units panels and 
joints may have to be carried out on site for the air-handling units to 
achieve the required leakage classification. Door locking mechanisms 
may also have to be adjusted.

Nuaire cannot be held responsible for the units failing a site leakage 
test if the above have not been carried out correctly.

6.3 Module Joints

After unwrapping, temporarily remove the rubber weatherproof cover 
strip and M10 base frame bolts from any modules and store in a safe 
location for later use.

Apply the sealing gasket as necessary to the mating faces of the 
unit frames. Typically the sealing gaskets are pre-fitted to the heat 
exchanger module; ancillary modules will be provided with a roll of 
sealing gasket for on-site fitting.

Make the unit joints in the following order:

Left and right hand side M10 bolts between the modules’ base 
frames (Figure 15).

Left and right hand side M6 Lower 3 axis alignment clamps (Figure 
16).

Left and right hand side M6 Middle 3 axis alignment clamps.

Left and right hand side M6 Upper 3 axis alignment clamps.

Air leakage, air blow marks to the unit casings and unacceptable 
noise levels could result if the correct installation procedures are not 
employed.

Prior to making the unit joints, you must ensure the base frames of 
adjoining modules are fully touching along the width of the unit.  
Failure to do so can result in deformation of the unit frame when 
using the three axis alignment clamps.

15 

M10 Modular Base Frame Connection Bolt

16 

3-Axis Clamp

6.4 Internal Connections

There are a number of internal connections that need to be completed 
prior to starting/commissioning the unit. These consist of all the wiring 
connections and the condensate hose (plate heat exchanger option 
only).

Please ensure that the condensate hose is connected between modules. 
Care must be taken to ensure a constant fall in gradient is maintained 
and the hose is kept taught (Figure 17).

Access is available in the fan plate to allow electrical/wiring 
connections to be made between modules (Figure 18).

When making the wiring connections, the sensor loop (Figure 19) must 
be removed and relocated to the end of the unit. 

17 

Condensate Hose Connection

Summary of Contents for BPS V-AT

Page 1: ...ufacturer its service agent or similarly qualified persons in order to avoid a hazard Precautions must be taken to avoid the back flow of gases into the room from the open flue of gas or other fuel bu...

Page 2: ...ce for installers and users of the BOXER PACKAGED SOLUTION BPS AHU units with heat recovery The BPS AHU range is manufactured from Aluzinc corrosion resistant steel with 50mm double skinned panels and...

Page 3: ...anded for Vertical PHX Units B AT FE R BPS size Frost Coil Electric 36kW Right Handed for Thermal Wheel Units B AT FE L BPS size Frost Coil Electric 36kW Left Handed for Thermal Wheel Units Frost Coil...

Page 4: ...m Only individual modules should be lifted or manoeuvred The units must not be lifted or manoeuvred pre assembled All base frame sections will have 50mm square lifting holes at the end of each side to...

Page 5: ...ndensate tray may be inspected and cleaned if necessary The LPHW and Electrical heater settings coil bleed and drain and all other control adjustments are similarly accessible Side access where possib...

Page 6: ...ht Hand Thermal Wheel Units SUPPLY SUPPLY CONTROLS Access 600mm Top View 14 Top View of Access For Right Hand Thermal Wheel Units 5 2 Access Areas 5 2 1 Left Hand Plate Heat Exchanger Units Open Extra...

Page 7: ...for the units failing a site leakage test if the above have not been carried out correctly 6 3 Module Joints After unwrapping temporarily remove the rubber weatherproof cover strip and M10 base frame...

Page 8: ...ent must not be exposed to the weather in an unassembled or partially assembled state All roof terminal ductwork sealing and assembly work must be completed before the unit can be considered weather r...

Page 9: ...t the requirement of removing the roof terminal Figure 21 6 11 Damper Roof Terminal Assembly The inlet outlet dampers and roof terminals are pre assembled for BPS sizes 07 12 and 17 on a double skinne...

Page 10: ...T 15 A 15 A 35 A 52 5 A 19 5 A 19 5 A 35 A 52 5 A B 42V AT 19 A 19 A 52 5 A 52 5 A 23 A 23 A 52 5 A 52 5 A B 42T AT 22 5 A 22 5 A 52 5 A 52 5 A 27 A 27 A 52 5 A 52 5 A Denotes any Character These heat...

Page 11: ...ddress 192 168 11 12 Subnet mask 255 255 255 0 LAN 011 node 012 7 7 Connection Chart Description iQ4E Terminal No 8DO Terminal No Di AI DO AO Fresh Air Sensor 1 4 5 1 Supply Air Sensor 2 6 7 1 Return...

Page 12: ...ocks 28 Removing a Conductor from a Terminal 7 9 4 Jumpers Terminal blocks can be commoned together to increase the number of terminals at the same potential using push in jumpers In these cases the t...

Page 13: ...heating and Reverse Cycle DX cooling Section 7 10 10 7 10 1 Code Description B 8 17 T L R AT L 1 2 3 4 5 6 7 8 1 Range B Boxer Packaged Solution 2 ErP Compliance Year 6 2016 8 or No Affix 2018 3 Unit...

Page 14: ...tion Heater Thermostat Supply Fan Extract Fan Controller Lighting Thermal Wheel Internal Connection are not shown for clarity 0 24V 15V 0 15V 230V 400V 400V 3ph 50Hz Main Power Supply Overcurrent Prot...

Page 15: ...l 0 24V 15V 0 15V 230V 400V 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolator L1 E L2 L3 N L1 L2 L3 N T1 T2 T3 N 1 2 3 4 Key Factory Connection Cu...

Page 16: ...n S2 S3 Mitsubishi Electric PAC IF012B E Interface HX Bypass Relay Fan Run Relays Controller Fuse 5A Condensate Pump Fuse 1A Aux Fuse 1A 24Vac Fuse 1 6A Lighting Thermal Wheel Terminal Extra Low Volta...

Page 17: ...ays Controller Fuse 5A Condensate Pump Fuse 1A Aux Fuse 1A 24Vac Fuse 1 6A Lighting Thermal Wheel Terminal Extra Low Voltage SL Enable UI5 0 10V Room Temperature Sensor Optional Note1 Anti Condensatio...

Page 18: ...ac Fuse 1 6A Lighting Thermal Wheel Terminal Extra Low Voltage SL Enable UI5 0 10V Room Temperature Sensor Optional Note1 Anti Condensation Heater Thermostat Supply Fan Extract Fan Controller Lighting...

Page 19: ...minal Extra Low Voltage SL Enable UI5 0 10V Room Temperature Sensor Optional Note1 Anti Condensation Heater Thermostat Supply Fan Extract Fan Controller Lighting Thermal Wheel 0 24V 15V 0 15V 230V 400...

Page 20: ...ote1 Anti Condensation Heater Thermostat Supply Fan Extract Fan Controller Lighting Thermal Wheel 0 24V 15V 0 15V 230V 400V 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotar...

Page 21: ...Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolator L1 E L2 L3 N L1 L2 L3 N T1 T2 T3 N 1 2 3 4 Key Factory Connection Customer Connection Mandatory Customer Co...

Page 22: ...ed the unit will increase the fans speeds as required until the pressure differential between the extract air and atmosphere reaches the constant pressure setpoint The pressure sensor is a 0 10v 0 100...

Page 23: ...dule module is provided in the Trend strategy When the schedule is on the heating output reverts to LPHW Electric heating The enable run on time must be set to 3 minutes for reverse cycle units This i...

Page 24: ...ecirc Force Recirc damper to recirc mode On Off Off 52 Damper NoRecirc Force Recirc damper out of recirc mode On Off Off Knob No Name Description Range Default 2 Run on Time Run on timer value 0 3600...

Page 25: ...maximum voltage to be supplied to the fan motor 6 10 v 10 v 41 CP Loop Gain Constant Pressure Loop Gain 0 50 0 5 42 IO Damper Delay Delay to allow inlet outlet dampers to open 0 300 sec 0 sec 43 Boos...

Page 26: ...e concentration and temperature of the air The space sensors have additional options of humidity monitoring and a 4 digit display The display will show the measured values in succession The duct senso...

Page 27: ...drawings for details of the type of fan and drive that is fitted Maintenance guidelines for all fans are beyond this manual please contact Nuaire for specific documents Before any work is carried out...

Page 28: ...Months Check filters and change clean if required failure to do so may impair the performance and energy efficiency of this unit Ensure condensate drains are cleaned clear and that water can flow fre...

Page 29: ...cool the switch will reset but a power cycle is required to reset the heater supply contactor The frost coil is fitted with a burst fired controller with integral set point air off thermistor air in f...

Page 30: ...ner pieces plastic heat exchangers packaging material and other plastic components can be segregated into mixed plastic and widely recycled Cardboard packaging wood used filters and other paper compon...

Page 31: ...te provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to duct work systems They must not be used to support the ductwork 4 4 Local Environment Humidity Am...

Page 32: ...32 01 09 21 Document Number 671746 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS V AT Installation Manual NOTES...

Reviews: