13
01. 09. 21. Document Number 671746
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
BPS V-AT
Installation Manual
5. Heating Type:
E = Electric
L = Low Pressure Hot Water (LPHW)
N = No Heating
6. Cooling Type:
C = Chilled Water (CW)
N = No Cooling
R = Reverse Cycle DX
X = DX*
7. Control Type:
AT = Adapt Trend
8. Access Handing
L = Left Hand
(in direction of supply
R = Right Hand
airflow)
*Condenser Unit and control by others.
7.10.2 Wiring Diagram Reference Table
Unit
Size
Unit WITHOUT
Electric Heater
or Reverse
cycle DX
Unit with
Electric
Heater
Unit with
Reverse
Cycle DX
Unit with Elec-
tric Heater &
Reverse Cycle
DX
07
Section 7.10.3
Section 7.10.4
Section 7.10.6
Section 7.10.9
12
Section 7.10.3
Section 7.10.4
Section 7.10.6
Section 7.10.9
17
Section 7.10.3
Section 7.10.4
Section 7.10.7
Section 7.10.10
22
Section 7.10.3
Section 7.10.4
Section 7.10.7
Section 7.10.10
32
Section 7.10.3
Section 7.10.5
Section 7.10.8
Section 7.10.11
42
Section 7.10.3
Section 7.10.5
Section 7.10.8
Section 7.10.11
7.10 Wiring Diagrams
A series of basic connection wiring diagrams have been provided to
assist on-site wiring. In order to reference the relevant diagrams please
use the code breakdown opposite to determine:
•
Unit size
•
If an electric heater is present
•
If Reverse Cycle DX heating or cooling is present.
The below tables can then be used to reference the required connection
and wiring diagrams.
Example:
Unit onsite has code
B822V/ER/AT-L.
This indicates a size 22 unit with
electric heating and Reverse Cycle DX cooling (Section 7.10.10).
7.10.1 Code Description:
B 8 17 T / L R / AT - L
| | | | | | | |
1 2 3 4 5 6 7 8
1. Range:
B = Boxer Packaged Solution
2. ErP Compliance Year:
6 = 2016
8 or No Affix = 2018
3. Unit Size:
07, 12, 17, 22, 32 or 42
4. Heat Recovery Type:
T = Thermal Wheel
V = Vertical Plate Exchanger
7.10.3 Unit Sizes 07 - 42 with No or LPHW Heating & No or CHW Cooling
ABB
0 0FF
ABB
0 0FF
ABB
0 0FF
ABB
0 0FF
ABB
0 0FF
ABB
0 0FF
ABB
0 0FF
ABB
0 0FF
N
L1 L2L3
E
24Vac 0V
* Note 1
Connect space temperature sensor in place of
extract temperature sensor for space
temperature control.
Condensate Pump HX
Bypass Relay
Fault Relay
Cool
Demand
Relay
Heat
Demand
Relay
Switched Live (Enable) 230Vac
Switched Live 2 (Boost) 230Vac
Aux 230Vac
E N L
Extra Low
Voltage
SL2
(Boost)
HX Bypass Relay
Fan Run Relays
Controller Fuse 5A
Condensate Pump Fuse 1A
Aux Fuse 1A
24Vac Fuse 1.6A
Lighting & Thermal
Wheel Terminal
Extra Low
Voltage
SL
(Enable)
UI5
0-10V
Room
Temperature
Sensor
(Optional)
*Note1
Anti-Condensation
Heater Thermostat
Supply Fan
Extract Fan
C
ontr
oller
Lighting &
Thermal
Wheel
Internal Connection are not shown for clarity.
0 24V
+15V 0 -15V 230V 400V
400V 3ph 50Hz
Main Power Supply
Overcurrent
Protection
(By Others)
Local R
otary Lockable IP66/67 Isolator
L1
E
L2 L3 N
L1 L2 L3 N
T1 T2 T3 N
1
2
3
4
If Applicable (Valve not supplied as standard)
24Vac LPHW Valve Supply (Constant)
0-10V LPHW Valve Demand (10V = 100%)
0V COM
If Applicable (Valve not supplied as standard)
24Vac CHW Valve Supply (Constant)
0-10V CHW Valve Demand (10V = 100%)
0V COM
Key:
Factory Connection
Customer Connection (Mandatory)
Customer Connection (Optional)
34
Unit Sizes 07 - 42 with No or LPHW Heating & No or CHW Cooling Wiring Diagram