8.18 Sensors & Touch Screen Controllers

To help you select the appropriate control solution for your application, 
simply refer to one of the options below. For the full range and 
technical details, please visit www.nuaire.co.uk.

8.18.1 Thermistor Temperature Sensors

Low cost thermistor sensors comprising insertion, clamp-on, and 
outside air versions. The insertion sensor may be used for duct or 
immersion purposes. It has a 6mm diameter brass probe which is 
suitable for retrofit immersion applications and will fit most existing 
pockets (universal fitting kit option).

Part Code: 

TB/TI/S

 - 

For duct or immersion use. Short 150mm 

  

TB/TI/L

 - 

For duct use only. Long 400mm.

Low cost

High quality thermistors

Brass probes

M20 conduit entry with M16 cable gland

IP67 housing

Quarter turn quick release lid

Easy to wire

Universal kit option for retrofit of immersion sensors

Adjustable insertion depth flange option for duct sensors

8.18.2 In Duct Humidity & Temperature Sensors

Duct mounted relative humidity and temperature sensors for HVAC 
applications. The certified 2% high accuracy (/2%) and standard 3% 
versions offer excellent linearity and stability over a wide humidity 
range (10 to 90 %RH).

Part Code: 

HT/D

 - 

Duct & Thermistor Sensor (+/-3%)

Pre-calibrated for ease of commissioning

IP65

Operates over 10 to 100 %RH non-condensing

± 3% accuracy versions

2 part connectors for ease of installation

Humidity sensor element protected by replaceable filter

Capacitive humidity sensing element provides excellent long term 

stability

Adjustable depth duct mounting flange option

8.18.3 CO

Sensors

The CO2 duct and space sensors monitor the carbon dioxide 
concentration and temperature of the air. The space sensors have 
additional options of humidity monitoring and a 4 digit display. The 
display will show the measured values in succession. The duct sensor 
has a quick-release lid to facilitate installation.

Part Code:          

CO2/T/D

 - 

Duct & Thermistor Sensor (+/-3%) 

 

           

CO2/T/S

 - 

Space CO2 Concentration & Temperature   

 

 

              Sensor

Pre-calibrated for ease of commissioning

IP65

Operates over 10 to 100 %RH non-condensing

± 3% accuracy versions

2 part connectors for ease of installation

Humidity sensor element protected by replaceable filter

Capacitive humidity sensing element provides excellent long term 

stability

Adjustable depth duct mounting flange option

8.18.4 Occupancy Sensors

The ceiling mounted OCC/U Ultrasonic Occupancy Detection System 
is specifically designed for combined HVAC and lighting control in open 
plan office environments. 

Part Code: 

OCC/UD/DC

 - 

Ultrasonic Detector, adjustable in 1  

 

 

 

           direction. 

  

OCC/UDA/DC

 - 

Ultrasonic Detector, adjustable in  

 

 

 

             2 directions.

Monitors occupancy over approximately 5 m diameter floor space

Fully automatic system operation

Direct connection to IQ Controllers

Lights never go off when needed (even detects hand movements)

Simple low cost installation

Extendable coverage of up to 10 detectors per IQ input

Corridor linking facility

8.18.5 Touch Screen Controllers 

 

44 

Available Sensors & Touchscreen Controllers

Thermistor Temperature Sensors

CO

2

 Sensor

SDU Display

IQVIEW4 Touch Screen Display

IQVIEW8 Touch Screen Display

Occupancy Sensors

In Duct Humidity & 

Temperature Sensors

SDU DISPLAY

 - 

(10 x 6 inch), 

RD/SDU-IQ2COMMSCABLE/3m

 - RJ11 

plug to RJ11 plug cable (3m) for SDU.

IQVIEW4 TOUCH SCREEN DISPLAY

 - 

(6 x 4 inch), 

FPK/Plate

 - 

Mounting Plate. 

IQVIEW 4-SM-BOX

 - 

Surface mount box for wall or panel. 

Transformer for IQVIEW4 included ACC/24V - 230/224 VAC, 36VA

IQVIEW8 TOUCH SCREEN DISPLAY

 - 

(10 x 6 inch). 

IQVIEW8BOX

 - 

Surface mount box for flat surfaces. 

Transformer for IQVIEW8 included ACC/24V - 230/224 VAC, 36VA

Summary of Contents for BPS V-AT

Page 1: ...ufacturer its service agent or similarly qualified persons in order to avoid a hazard Precautions must be taken to avoid the back flow of gases into the room from the open flue of gas or other fuel bu...

Page 2: ...ce for installers and users of the BOXER PACKAGED SOLUTION BPS AHU units with heat recovery The BPS AHU range is manufactured from Aluzinc corrosion resistant steel with 50mm double skinned panels and...

Page 3: ...anded for Vertical PHX Units B AT FE R BPS size Frost Coil Electric 36kW Right Handed for Thermal Wheel Units B AT FE L BPS size Frost Coil Electric 36kW Left Handed for Thermal Wheel Units Frost Coil...

Page 4: ...m Only individual modules should be lifted or manoeuvred The units must not be lifted or manoeuvred pre assembled All base frame sections will have 50mm square lifting holes at the end of each side to...

Page 5: ...ndensate tray may be inspected and cleaned if necessary The LPHW and Electrical heater settings coil bleed and drain and all other control adjustments are similarly accessible Side access where possib...

Page 6: ...ht Hand Thermal Wheel Units SUPPLY SUPPLY CONTROLS Access 600mm Top View 14 Top View of Access For Right Hand Thermal Wheel Units 5 2 Access Areas 5 2 1 Left Hand Plate Heat Exchanger Units Open Extra...

Page 7: ...for the units failing a site leakage test if the above have not been carried out correctly 6 3 Module Joints After unwrapping temporarily remove the rubber weatherproof cover strip and M10 base frame...

Page 8: ...ent must not be exposed to the weather in an unassembled or partially assembled state All roof terminal ductwork sealing and assembly work must be completed before the unit can be considered weather r...

Page 9: ...t the requirement of removing the roof terminal Figure 21 6 11 Damper Roof Terminal Assembly The inlet outlet dampers and roof terminals are pre assembled for BPS sizes 07 12 and 17 on a double skinne...

Page 10: ...T 15 A 15 A 35 A 52 5 A 19 5 A 19 5 A 35 A 52 5 A B 42V AT 19 A 19 A 52 5 A 52 5 A 23 A 23 A 52 5 A 52 5 A B 42T AT 22 5 A 22 5 A 52 5 A 52 5 A 27 A 27 A 52 5 A 52 5 A Denotes any Character These heat...

Page 11: ...ddress 192 168 11 12 Subnet mask 255 255 255 0 LAN 011 node 012 7 7 Connection Chart Description iQ4E Terminal No 8DO Terminal No Di AI DO AO Fresh Air Sensor 1 4 5 1 Supply Air Sensor 2 6 7 1 Return...

Page 12: ...ocks 28 Removing a Conductor from a Terminal 7 9 4 Jumpers Terminal blocks can be commoned together to increase the number of terminals at the same potential using push in jumpers In these cases the t...

Page 13: ...heating and Reverse Cycle DX cooling Section 7 10 10 7 10 1 Code Description B 8 17 T L R AT L 1 2 3 4 5 6 7 8 1 Range B Boxer Packaged Solution 2 ErP Compliance Year 6 2016 8 or No Affix 2018 3 Unit...

Page 14: ...tion Heater Thermostat Supply Fan Extract Fan Controller Lighting Thermal Wheel Internal Connection are not shown for clarity 0 24V 15V 0 15V 230V 400V 400V 3ph 50Hz Main Power Supply Overcurrent Prot...

Page 15: ...l 0 24V 15V 0 15V 230V 400V 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolator L1 E L2 L3 N L1 L2 L3 N T1 T2 T3 N 1 2 3 4 Key Factory Connection Cu...

Page 16: ...n S2 S3 Mitsubishi Electric PAC IF012B E Interface HX Bypass Relay Fan Run Relays Controller Fuse 5A Condensate Pump Fuse 1A Aux Fuse 1A 24Vac Fuse 1 6A Lighting Thermal Wheel Terminal Extra Low Volta...

Page 17: ...ays Controller Fuse 5A Condensate Pump Fuse 1A Aux Fuse 1A 24Vac Fuse 1 6A Lighting Thermal Wheel Terminal Extra Low Voltage SL Enable UI5 0 10V Room Temperature Sensor Optional Note1 Anti Condensatio...

Page 18: ...ac Fuse 1 6A Lighting Thermal Wheel Terminal Extra Low Voltage SL Enable UI5 0 10V Room Temperature Sensor Optional Note1 Anti Condensation Heater Thermostat Supply Fan Extract Fan Controller Lighting...

Page 19: ...minal Extra Low Voltage SL Enable UI5 0 10V Room Temperature Sensor Optional Note1 Anti Condensation Heater Thermostat Supply Fan Extract Fan Controller Lighting Thermal Wheel 0 24V 15V 0 15V 230V 400...

Page 20: ...ote1 Anti Condensation Heater Thermostat Supply Fan Extract Fan Controller Lighting Thermal Wheel 0 24V 15V 0 15V 230V 400V 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotar...

Page 21: ...Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolator L1 E L2 L3 N L1 L2 L3 N T1 T2 T3 N 1 2 3 4 Key Factory Connection Customer Connection Mandatory Customer Co...

Page 22: ...ed the unit will increase the fans speeds as required until the pressure differential between the extract air and atmosphere reaches the constant pressure setpoint The pressure sensor is a 0 10v 0 100...

Page 23: ...dule module is provided in the Trend strategy When the schedule is on the heating output reverts to LPHW Electric heating The enable run on time must be set to 3 minutes for reverse cycle units This i...

Page 24: ...ecirc Force Recirc damper to recirc mode On Off Off 52 Damper NoRecirc Force Recirc damper out of recirc mode On Off Off Knob No Name Description Range Default 2 Run on Time Run on timer value 0 3600...

Page 25: ...maximum voltage to be supplied to the fan motor 6 10 v 10 v 41 CP Loop Gain Constant Pressure Loop Gain 0 50 0 5 42 IO Damper Delay Delay to allow inlet outlet dampers to open 0 300 sec 0 sec 43 Boos...

Page 26: ...e concentration and temperature of the air The space sensors have additional options of humidity monitoring and a 4 digit display The display will show the measured values in succession The duct senso...

Page 27: ...drawings for details of the type of fan and drive that is fitted Maintenance guidelines for all fans are beyond this manual please contact Nuaire for specific documents Before any work is carried out...

Page 28: ...Months Check filters and change clean if required failure to do so may impair the performance and energy efficiency of this unit Ensure condensate drains are cleaned clear and that water can flow fre...

Page 29: ...cool the switch will reset but a power cycle is required to reset the heater supply contactor The frost coil is fitted with a burst fired controller with integral set point air off thermistor air in f...

Page 30: ...ner pieces plastic heat exchangers packaging material and other plastic components can be segregated into mixed plastic and widely recycled Cardboard packaging wood used filters and other paper compon...

Page 31: ...te provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to duct work systems They must not be used to support the ductwork 4 4 Local Environment Humidity Am...

Page 32: ...32 01 09 21 Document Number 671746 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS V AT Installation Manual NOTES...

Reviews: