40
30. 07. 20. Document Number 671760
Nuaire |
Western Industrial Estate
|
Caerphilly
|
CF83 1NA
|
nuaire.co.uk
BPS V-CO
Installation Manual
9.10 Setting Pages
These set of pages allow the user to configure the technical functions of the LCD both from the BACnet and user interface perspectives.
The settings page requires a service password for access.
9.10.1 Network Settings Page
Allow the user to discover all devices connected on the MS/TP network and browse all objects exposed within these devices.
Parameter Name
Description
Default Setting
Device Name
It defines the BACnet Device Object Name
FAD0351
Device ID
It defines the BACnet Device Object Identifier
127
MAC Address
MSTP Address of FAD
127
Descriptions
BACnet Description of FAD
Field Advanced Display
Baud Rate
It defines the FAD communication speed over the BACnet local
network.
38400
Max Info Frames
It defines the BACnet Device Object Max_Info_Frames
3
Adjust Priority
The Adjust priority parameter defines with which priority the display
will command AV / BV / MV values.
16
Override Priority
The Override priority parameter defines with which priority the
display will command AO / BO / MO values
8
Page Refresh Time
It defines the polling speed at which the FAD will refresh the values
shown on the screen
30 sec
Max Master
This parameter represents the value of the Max_Master property of
the node’s Device object
127
APDU Time
The APDU Timeout property defines the amount of time,
in seconds, the FAD waits for responses from other devices.
3
9.10.2 Display Settings Page
Parameter Name
Description
Default Setting
Backlight
It defines whether the back light remains ON or turns OFF during
Standby
Stand-By ON
Homepage
It defines which page to show at power up or pressing the
“Home” shortcut button
Main Menu
Service Password
Password required to enter settings page
0
User Password
Password Required to change locked values
(All values are locked by default)
0
Stand By
It defines the behaviour of the display once the “Stand By Timer”
has expired without interactions from the user
-
Stand By Timer
It defines the inactivity period, in minutes, required to force
the display in Stand By mode and for both Service and User
passwords expiration. Defining this parameter to Zero, the
passwords request (if any) is prompted at any access to pages
requiring them
0 min
Feedback Sound
It defines whether the device shall provide a sound feedback
during user interaction
OFF
Alarm
It defines whether the device shall provide a sound feedback
when receiving a new Alarm. The notification sound can be
continuous (ON) or intermittent (BEEP)
OFF
Date
It adjusts settings related to the Day, Month and Year of the
FAD integrated clock
Time
It adjusts settings related to the Hour and Minute of the
FAD integrated clock
Day Of Week
It adjusts settings related to the Day of Week (1-7) of the
FAD integrated clock