32
30. 07. 20. Document Number 671760
Nuaire |
Western Industrial Estate
|
Caerphilly
|
CF83 1NA
|
nuaire.co.uk
BPS V-CO
Installation Manual
8.38.18 Zone Sensors
LCD Browser
Page
BACnet Object
Description
Object
Type
Object
ID
Default
Value
Units
2
RM199 Temp
The temperature at RM address 199
AI
10029
N/A
Degrees-Celsius
2
RM199 Humidity
The Humidity at RM address 199
AI
10017
N/A
Percent-Relative-Humidity
7
RM199 Setpoint
The setpoint at RM address 199
AV
10023
N/A
Degrees-Celsius
28
RM199 Fan Speed
Fan Speed Override Status of RM199
MSV
10014
N/A
(1)Auto (2)Off (3)Low (4)
Medium (5)High
37
RM199 Fan Display
Fan Speed Override Display at RM address
199
MSV
14703
N/A
(1)No Status (2)Off (3)Low
(4)Medium (5)High (6)Auto-
Off (7)Auto-Low (8)Auto-
Medium (9)Auto-High
3
RM200 Temp
The temperature at RM address 200
AI
10050
N/A
Degrees-Celsius
3
RM200 Humidity
The Humidity at RM address 200
AI
10053
N/A
Percent-Relative-Humidity
7
RM200 Setpoint
The setpoint at RM address 200
AV
10074
N/A
Degrees-Celsius
3
RM201 Temp
The temperature at RM address 201
AI
10065
N/A
Degrees-Celsius
4
RM201 Humidity
The Humidity at RM address 201
AI
10077
N/A
Percent-Relative-Humidity
7
RM201 Setpoint
The setpoint at RM address 201
AV
10083
N/A
Degrees-Celsius
3
RM202 Temp
The temperature at RM address 202
AI
10068
N/A
Degrees-Celsius
4
RM202 Humidity
The Humidity at RM address 202
AI
10092
N/A
Percent-Relative-Humidity
7
RM202 Setpoint
The setpoint at RM address 202
AV
10098
N/A
Degrees-Celsius
4
RM203 Temp
The temperature at RM address 203
AI
10071
N/A
Degrees-Celsius
4
RM203 Humidity
The Humidity at RM address 203
AI
10107
N/A
Percent-Relative-Humidity
8
RM203 Setpoint
The setpoint at RM address 203
AV
10113
N/A
Degrees-Celsius
5
RM212 CO2
The CO2 at RM address 212
AI
10137
N/A
Parts-Per-Million
5
RM213 CO2
The CO2 at RM address 213
AI
10140
N/A
Parts-Per-Million
5
RM214 CO2
The CO2 at RM address 214
AI
10143
N/A
Parts-Per-Million
5
RM215 CO2
The CO2 at RM address 215
AI
10146
N/A
Parts-Per-Million
8.38.19 Frost Protection
10
Frost Prot. Fan Off
Minimum time the supply fan will stop in a
frost protection state
AV
10274
300
Seconds
11
Frost Prot. Temp
Supply temperature at which frost
protection becomes active
AV
10275
4
Degrees-Celsius
8.38.20 Hibernate Mode
34
Hibernate Mode
Unit is ready for hibernation
MSV
10241
Off
(1)Off (2)On
8.38.21 Purge Mode
35
Purge Active
This input will enable purge mode
MSV
10243
Off
(1)Off (2)On
13
Purge Fan Speed
Purge Fan Speed
AV
10304
60
Percent
13
Purge Min Temp
The minimum temperature that will stop
night cooling
AV
10305
12
Degrees-Celsius
26
Purge Time Schedule Purge Time Schedule
SCH
10499
N/A
0
37
Purge Time Schedule State of the Purge Time Schedule
MSV
10512
N/A
(1)Off (2)On
8.38.22 Night Cool Mode
35
Night C Mode
This input will enable night cool mode.
MSV
10242
Off
(1)Off (2)On
12
Night C Fan Speed
The night cool fan speed
AV
10281
60
Percent
12
Nigh C Min Temp
The minimum temperature that will stop
night cooling
AV
10302
12
Degrees-Celsius
27
Night C Schedule
Night Cooling Schedule
SCH
16014
N/A
0
27
Night C Schedule
Night Cooling Schedule
SCH
16014
N/A
0
26
Night C Sample
Daytime schedule for winter or summer
decision making
SCH
15875
N/A
0
38
Night C Sample
Night Cooling Sample Schedule
MSV
16008
N/A
(1)Off (2)On