10.5 Sensor Addressing
ESCO-TDFS has a fixed device address of 199 on the SA Bus. The
address can be changed on other models via DIP switches on the PCB
rear. The designation of each address is shown in the following table.
Network Page
Description
Module Type
199
Fixed
Multi-function (with Fan Speed
Override)
200-203
Adjustable
Multi-function
212-219
Adjustable
Room CO2 Sensor Module
Each sensor on the SA bus must have a unique address. The default
controller strategy is preconfigured to automatically detect all Room
Modules on the network and react accordingly.
ON
(Closed)
OFF
(Open)
Address
Switch Settings
Switch 2
Switch 1
200
OFF
OFF
201
OFF
ON
202
ON
OFF
203
ON
ON
41
200-203 Address Switch Settings
Address
Switch Settings
Switch 4
Switch 2
Switch 1
212
OFF
OFF
OFF
213
OFF
OFF
ON
214
OFF
ON
OFF
215
OFF
ON
ON
Not Supported
ON
ANY
ANY
42
212-215 Address Switch Settings
ON
(Closed)
OFF
(Open)
ON
(Closed)
OFF
(Open)
10.6 Room Module Technical Specifications
Supply Voltage
15VDC (Powered from SA bus)
Temperature Measurement Range
0 to 40°C
Humidity Measruement Range
0 to 100% (Full)
10 to 90% (Calibrated)
Temperature Sensor Type
Local 1k ohm Platinum
Resistance Temerature
Detector (RTD);
Class A per IEC 60751
Humidity Sensor Type
Thin Film Capacitive Sensor
Temperature Resolution (Models with
LCD)
±0.5°C
Default Temperature Setpoint
Adjustment Range
10 to 30°C
PIR Occupancy Sensor Motion Detection
Minimum 94 Angular Degrees up
to a distance of 15 ft (4.6m);
Based on a clear line of sight.
Ambient Operating Conditions
10 to 30°C, 10 to 90% RH
(Temp Probe -10 to 60°C)
Ambient Storage Conditions
-20 to 60°C, t to 95% RH
CO2 Sensor Warmup Time
Less than 1 Minute; less than 10
minutes for full accuracy.
10.7 Interconnection
The sensors or other devices on the SA bus network connect either by
modular RJ12 connections or by screwed terminals using plain ended
cable. All sensors are fitted with both.
10.7.1 Modular Cable (Up To 30m)
The Room Modules can connect using a 24AWG twisted 3-pair cable
with RJ12 connections over the Sensor Actuator (SA) bus. the following
items are available.
ESCO-C3M
3m Prefabricated sensor cable with modular jacks
ESCO-C5M
5m Prefabricated sensor cable with modular jacks
ESCO-C10M
10m Prefabricated sensor cable with modular jacks
ESCO-C20M
20m Prefabricated sensor cable with modular jacks
ESCO-C30M
30m Prefabricated sensor cable with modular jacks
ESCO-2WA
2-port extension adapter
ESCO-3WA
3-port extension adapter
Room Modules must not be fitted more than 30metres (cable length)
from the controller when using this connection method.
10.7.2 Plain Cable (30 - 150m)
If a Room Module is to be fitted more than 30metres (cable length)
from a controller, the following cable is recommended.
ESCO-MSTPC30M
Ecosmart Connect MSTP cable reel 30m
ESCO-MSTPC150M
Ecosmart Connect MSTP cable reel 150M
On the SA Bus, the + and - wire are one twisted pair, and the COM
and SA PWR are the second twisted pair of wires.
These cannot be used with RJ12 connections and must be stripped and
connected using screwed terminals. The shield must be earthed at the
control panel end only and be made continuous along the bus length.
Room Modules must not be fitted more than 150metres (cable length)
from the controller.