BPS V-CO
Installation Manual
8.38.9 Fan Outputs
LCD Browser
Page
BACnet Object
Description
Object
Type
Object
ID
Default
Value
Units
6
Supply Fan Output
The 0-10v signal to the supply fan
AO
10182
N/A
volts
6
Extract Fan Output
The 0-10v signal to the extract fan
AO
10176
N/A
volts
21
Fan Enabled Cmd
The state of the fan enabled relay.
BO
10191
N/A
(1)Off (2)On
8.38.10 Fan Commissioning
9
Extract Fan Max
Individual fan maximum speed setting
AV
10268
100
Percent
10
Extract Fan Min
Individual fan minimum speed setting
AV
10270
20
Percent
15
Supply Fan Max
Individual fan maximum speed setting
AV
10312
100
Percent
15
Supply Fan Min
Individual fan minimum speed setting
AV
10314
20
Percent
8.38.11 Temperature Control
14
Software Setpoint
Software Setpoint
AV
10309
22
Degrees-Celsius
9
Deadband
Dead band for temp control
AV
10266
3
Degrees-Celsius
33
SetPoint Op
Setpoint operation
MSV
10214
Software Only (1)Last Changed (2)Software
Only (3)Last Changed with
Timeout
19
Setpoint Timeout
The time before reverting to software
setpoint when last changed with timeout is
selected.
AV
17971
3600
seconds
27
Setpoint Schedule
A schedule for setpoint adjustment.
SCH
18215
N/A
0
19
Setpoint Schedule
Current state of the Setpoint Schedule
object.
AV
18215-
22
Degrees-Celsius
33
T Sens. Op
Temperature sensor operation
MSV
10215
NS Average
(1)NS Average (2)Return Air
Only (3)NS & Return Average
33
0-10v Temp Range
Temperature sensor range
MSV
10216
0 to 50°C
(1)0 to 50°C (2)0 to 40°C
(3)0 to 100°C (4)0 to 80°C
(5)0 to 90°C
35
Temp Control Mode
Temperature control mode
MSV
10245
Supply Temp
(1)Supply Temp (2)Room
Temp
14
STC H/C Pref
STC Heat/Cool Pref
AV
10310
50
No units
15
STC HX Efficiency
STC HX Efficiency
AV
10311
0.8
No units
13
RTC Boost Band
The Return Temperature Control Boost Band AV
10306
15
Degrees-Celsius
14
RTC Max Supply
Temp
Maximum supply temp when in RTC mode
AV
10307
35
Degrees-Celsius
14
RTC Min Supply
Temp
Minimum supply temp when in RTC mode
AV
10308
12
Degrees-Celsius
8.38.12 Heating Output
31
Heating Type
Set the type of heating fitted.
MSV
10206
As Per Build
(1)None (2)LPHW (3)Electric
(4)3rd-Party
6
Heating Output
The 0-10v signal to the heating output.
AO
10179
N/A
Percent
8.38.13 Cooling / Configurable Outfits
30
Cooling Type
Set the type of cooling fitted.
MSV
10203
None
(1)None (2)Chilled Water
(3)3rd-Party (4)Reverse Cycle
DX
22
Cooling Demand
Cmd
The state of the cooling demand relay.
BO
10194
N/A
(1)Off (2)On
43
OUT4 Mode
Chooses the mode of Analogue Output 4
MSV
17608
Cooling
Demand
(1)Cooling Demand (2)
ESClassic BMS Mode
6
Output 4
Configurable output 4 (OUT4)
AO
10173
N/A
Percent
44
ESC BMS Thermic
Output
Chooses whether to demand thermal
output in 0-10v ESClassic BMS mode
MSV
17610
Auto
(1)Auto (2)None (3)Heating
(4)Cooling