BPS V-CO
Installation Manual
8.38.14 HX Bypass Damper
LCD Browser
Page
BACnet Object
Description
Object
Type
Object
ID
Default
Value
Units
21
Bypass Damper Cmd The controller’s signal to the HX bypass.
(Active = Bypass, Inactive = Heat Exchange)
BO
10185
N/A
(1)Inactive (2)Active
8.38.15 Fan Demand Inputs
18
Fan Speed Demand
A user entered fan speed demand. 0% =
trickle speed
AV
17761
0
Percent
18
BMS 0-10v Input
A virtual BMS voltage input using an
ESClassic BMS table
AV
17773
0
Volts
27
Fan Speed Schedule
A schedule for fan speed demand (0% =
Trickle speed)
SCH
17798
N/A
0
18
Fan Speed Schedule
Current state of the Fan Speed Demand
Schedule object.
AV
17830
0
Percent
44
Fan Override
Operation
Chooses the operation of the 3-speed fan
override.
MSV
17975
Override Has
Priority
(1)Overide Has Priority (2)
Revert to Auto after Timeout
19
Fan Override
Timeout
The time before reverting to auto fan
speed when revert to auto with timeout is
selected.
AV
17977
3600
seconds
9
CO2 Target
Target CO2 Value
AV
10265
650
Parts-per-million
29
0-10 v CO2 Range
CO2 sensor output range
MSV
10200
N/A
(1)0-2,000ppm (2)0-
4,000ppm (3)0-5,000ppm
(4)0-10,000ppm (5)0-
20,000ppm
29
CO2 Sensor Op
CO2 sensor operation
MSV
10201
N/A
(1)Average CO2 (2)Max CO2
(3)Ignore CO2
11
Humidity Target
Relative Humidity Target
AV
10278
50
Percent-relative-Humidity
31
H Sensor Op
Humidity Sensor Operation
MSV
10207
Average RH%
(1)Average RH% (2)Max RH%
(3)Ignore RH%
13
Pressure Target
Target pressure value
AV
10303
400
Pascals
32
0-10v Press. Range
Pressure sensor range
MSV
10212
0 to 1000Pa
(1)0-25Pa (2)0-50Pa
(3)0-100Pa (4)0-300Pa
(5)0-500Pa (6)0-1000Pa
(7)0-1600Pa (8)0-2500Pa
(9)0-3000Pa
32
P sens. Op
Pressure sensor operation
MSV
10213
Average Value
(1)Average (2)Max (3)Ignore
8.38.16 Selected Process Variables
16
Room Air Temp
The room air temperature
AV
11296
N/A
Degrees-Celsius
16
CO2 Level
The CO2 Level
AV
13980
N/A
ppm
16
Humidity
The Humidity Level
AV
14297
N/A
% RH
16
Active Setpoint
The setpoint currently used
AV
14534
N/A
Degrees-Celsius
8.38.17 Unit Temperature Sensors
1
Supply Air Temp (B)
The supply air temperature
AI
10005
N/A
Degrees-Celsius
1
Fresh Air Temp (H)
The fresh air temperature
AI
10008
N/A
Degrees-Celsius
1
Extract Air Temp (C)
The extract air temperature
AI
10011
N/A
Degrees-Celsius