BPS V-CO
Installation Manual
8.38 BACnet Object List (By Category
)
8.38.1 Enable
LCD Browser
Page
BACnet Object
Description
Object Type Object ID
Default
Value
Units
34
Enable
Software enable switch
MSV
10218
Off
(1)Off (2)On
20
SL Enable
The state of the enable input (IN8)
BI
10161
N/A
(1)Off (2)On
9
Run-on (Enable)
Run-on timer value
AV
10267
0
Seconds
24
Local Calendar
0
CAL
10496
N/A
0
34
Enable via Schedule
Enabled via Schedule
MSV
10219
N/A
(1)Off (2)On
8.38.2 Trickle Mode
37
Trickle Mode
Enable trickle mode
MSV
10250
Off
(1)Off (2)On
15
Trickle Deadband
Setpoint deadband used when trickling
with no enable signal.
AV
10316
5
Degrees-Celsius
8.38.3 IO Dampers
44
IO Damper Fitted
Selects whether IO dampers are fitted on
alarm circuit 2
MSV
17669
No
(1)No (2)Yes
12
IO Damper Delay
Delay between starting the fan relay and
the fan output.
AV
10279
0
Seconds
8.38.4 Analogue Inputs
2
IN4
The 0-10 voltage at input 4
AI
10032
N/A
volts
31
IN4 Function
Function of the UI4 input
MSV
10209
None
(1)None (2)N/A (3)N/A
(4)0-10V CO2 Sensor
(5)0-10V Temperature
Sensor (6)0-10V
Humidity Sensor
(7)0-10V Pressure Sensor
2
IN5
The 0-10 voltage at input 5
AI
10035
N/A
volts
32
IN5 Function
Function of the UI5 input
MSV
10210
None
(1)None (2)Fan Speed
Control (3)0-10v BMS
(4)0-10V CO2 Sensor
(5)0-10V Temperature
Sensor (6)0-10V
Humidity Sensor
(7)0-10V Pressure Sensor
8.38.5 Configurable Inputs
20
SL2 Input
The state of the configurable input (IN9)
BI
10164
N/A
(1)Off (2)On
30
SL2 Mode
Set the function of switched live 2
MSV
10202
Fan Boost
(1)None (2)Fan Boost (3)
Heater Boost (4)Extract
Setback
8.38.6 Fan Boost
34
Fan Boost
Software enabled Fan boost
MSV
10240
Off
(1)Off (2)On
10
Run-on (Boost)
Boost run-on time
AV
10272
0
Seconds
10
Supply Fan Boost
Speed
Supply Fan boost speed
AV
10273
100
Percent
18
Extract Boost Speed
The extract fan boost speed
AV
17419
100
Percent
8.38.7 Heat Boost
30
Heat Boost
Software enabled Heater boost
MSV
10205
Off
(1)Off (2)On
11
Heat Boost Setpoint
Heater Boost Setpoint
AV
10276
35
Degrees-Celsius
8.38.8 Extract Setback
44
Extract Setback
Puts the extract fan to setback speed
MSV
17769
Off
(1)Off (2)On
20
Extract Setback Speed The extract fan speed when Extract Setback
is enabled.
AV
18258
30
Percent