background image

26

30. 07. 20. Document Number  671760

Nuaire | 

Western Industrial Estate 

Caerphilly 

CF83 1NA 

|

 

nuaire.co.uk

BPS V-CO

Installation Manual

8.23.2 Maintenance Alarm (Non-Latching)

Once in maintenance alarm state the only action taken is de-energising 
of the fault relay. Once the trigger is removed, the alarm will reset 
automatically.

Causes of maintenance alarm:

Sensor Failure.

Low supply temperature, default 8°C. This can be set to stop fans 

if required.

Frost protection routine active, default 4°C (This only runs if water 

valves are selected as fitted.

Excessively high supply temperature reading (This will stop 

heating).

Filter dP fault (if fitted).

All alarms have a hold off period set by the setpoint “Alarm delay”.

8.23.3 Thermal Trip

In case of software failure, as a final resort, the electric heater is 
protected by a fail-safe thermal overload switch. This switch disables 
the heater controller via a contactor once the temperature reaches 
80°C. When this occurs, the critical alarm will latch in software and the 
supply contactor will latch in the off position.

Once the unit cools, the contactor will remain latched off until power 
cycle.

8.24 Configurable Relay 8 (RL8)

Relay 8 is a configurable relay output which can be set to the following 
functions. It can be set by the multi-state object “RL8 Mode”.

Cooling Demand (Default Setting)

 

This option will run the Relay as a cooling command relay. This 
output will only function if a cooling type is selected.

Window Actuator

 

This option will run a Window Indication routine with a dual CO2 
setpoint strategy. Relay 8 will be used to indicate to the end user 
whether it is appropriate to open the windows or not. This relay 
can be wired to an end user’s signal lamp or other signal. This relay 
is SPST so an additional relay is required if a light is required for 
each state. A multistate object, ‘Window Mode Status’, exists with 
two states, ‘Open’ and ‘Close’.

At external temperatures less than the ‘Window Open Threshold’ 
(14°C default) the indicator will signal close windows. The ‘CO2 Winter 
Target’ will be used as the setpoint (1000ppm default).  

At external temperatures greater than the ‘Window Open Threshold’ 
(14°C default) and CO2 level higher than the ‘CO2 Winter Target’, the 
indicator will signal open windows. The ‘CO2 Summer Target’ will be 
used as the setpoint (1500ppm default).

If the HX bypass damper is driven to bypass while fans are enabled, 
the indicator will signal open windows (HX Bypass due to Condensate 
pump failure will not affect windows status).

The ‘Window Mode Status’ will indicate close windows when the unit is 
not enabled and at all other times.

8.25 Configurable Analogue Output 4 (OUT4)

OUT4 is a configurable analogue output which can be set to the 
following functions via the multi-state object “OUT4 Mode”.

Cooling Demand (Default Setting)

 

This will provide a standard 0-10V cooling output. This output will 
only function if a cooling type is selected. 

ES Classic BMS

 

This option will provide a 0-10v ESClassic BMS output based on 
ventilation demand. This can then be used in conjunction with 
the fan run relay to run multiple slave Classic units from a master 
Connect control.

The type of BMS output can be selected by the muti-state object ‘ECS 
BMS Thermic Output’.

Auto 

-   The BMS output will switch between heating and cooling 

 

 

depending on outdoor air temperature.

None

 -   The unit will only supply ‘Vent Only’ voltages.

Heating

 - The unit will only supply ‘Heating’ voltages.

Cooling

 - The unit will only supply ‘Cooling’ voltages.

8.25.1 ES Classic BMS Output Table

Function

Ventilation Only

Cooling

Heating

Off / Trickle

0.25V

-

-

Speed 1

0.5V

0.75V

1V

Speed 2

1.5V

1.75V

2V

Speed 3

2.5V

2.75V

3V

Speed 4

3.5V

3.75V

4V

Speed 5

4.5V

4.75V

5V

Speed 6

5.5V

5.75V

6V

Speed 7

6.5V

6.75V

7V

Speed 8

7.5V

7.75V

8V

Speed 9

8.5V

8.75V

9V

Speed 10

9.5V

9.75V

10V

8.26 Fire Alarm

Once the Fire Alarm object is switched to the Alarm State, all fans, 
heating and cooling elements will stop instantly. The fault relay 
will de-energise and a fault message will be sent to the ESCO-LCD. 
Once the fire alarm status is released, the units will continue running 
automatically.

8.27 BACnet Overview

BACnet is a data communication protocol for Building Automation and 
Control Networks. It allows compatibility between devices of different 
manufacturers.

In BACnet, any device on the network has the ability to browse the 
network and discover devices.

8.28 Writing Values

It is best practice to only write to AV, BV & MSV (Analogue Variables, 
Binary Variables, and Multistate Variables). When writing to these, it is 
best to write at priority level 16.

8.29 Typical Basic Commissioning

Set the analogue variables “Extract Fan Min Speed” “Supply Fan 
Min Speed” “Extract Fan Max Speed” “Supply Fan Max Speed” 
during commissioning. 

If flow measurements are required enable the unit using the 
“Enable” MSV and boost the unit using the “Fan Boost” MSV.

Summary of Contents for B 07T/CO Series

Page 1: ...be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard Precautions must be taken to avoid the back flow of gases into the room from the open flue...

Page 2: ...l heating LPHW Electric or Reverse Cycle DX and cooling Chilled Water or Reverse Cycle DX model variants are available The Reverse Cycle coils are supplied as standard with inbuilt PAC Control and opt...

Page 3: ...shorter modules the fork lifting points will be along the length of the section without a covered channel Figure 2 Palletised Forklift Assembly with base frame Slings via spreaders fitted to unit wit...

Page 4: ...s or exhaust ventilators Once assembled and in position sufficient free space must be available adjacent to the unit for future inspection maintenance component service repair and replacement and conn...

Page 5: ...r to operating the unit by moving the belt drive motor from its transport to operating position 4 7 Weather Resistant Units The units are supplied in multiple sections and have weather resistant roof...

Page 6: ...that may be attached to the fan or motor base frame and that all traps are primed Close all access door seals for damage and replace any panels that have been removed IMPORTANT If a frost coil is not...

Page 7: ...ts B AT FE R BPS size Frost Coil Electric 36kW Right Handed for Thermal Wheel Units B AT FE L BPS size Frost Coil Electric 36kW Left Handed for Thermal Wheel Units Frost Coil LPHW 3 B AV FL R BPS size...

Page 8: ...ndensate tray may be inspected and cleaned if necessary The LPHW and Electrical heater settings coil bleed and drain and all other control adjustments are similarly accessible Side access where possib...

Page 9: ...Unit Right Hand Unit Open Exhaust Open Exhaust Open Extract Open Exhaust Open Exhaust 48 49 53 50 51 52 54 55 Access For Left Hand Plate Heat Exchanger Units Top View of Access For Left Hand Plate Hea...

Page 10: ...supply contactor 7 3 Unit Power Supply Details FLC Denotes any Character These heater models require a separate power supply for the electric heater section with an appropriate over current protection...

Page 11: ...are located on the sides of the units Description iQ4E Terminal No 8DO Terminal No Di AI DO AO Fresh Air Sensor 1 4 5 1 Supply Air Sensor 2 6 7 1 Return Room Air Sensor 3 8 9 1 Input 4 4 10 11 1 Inpu...

Page 12: ...jumpers In these cases the terminals are treated as one conductor 7 8 5 Jumper Removal Insert the operating tool blade between the jumper and the partition wall of the dual jumper slots then lift up t...

Page 13: ...230V 400V 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolator L1 E L2 L3 N L1 L2 L3 N T1 T2 T3 N 1 2 3 4 Key Factory Connection Customer Connection...

Page 14: ...Customer Connection Mandatory Customer Connection Optional FC BUS 100 240V RELAY RELAY RELAY RELAY RELAY CONFIGURABLE COM SHD COM HOT OUT9 NO OCOM9 OUT8 NO OCOM8 OUT7 NO OCOM7 OCOM6 OUT6 NC OUT5 NC OU...

Page 15: ...RELAY RELAY RELAY RELAY RELAY CONFIGURABLE COM SHD COM HOT OUT9 NO OCOM9 OUT8 NO OCOM8 OUT7 NO OCOM7 OCOM6 OUT6 NC OUT5 NC OUT6 NO OUT5 NO OCOM5 OUT4 OCOM4 OUT3 OCOM3 OUT2 OCOM2 OUT1 OCOM1 COM POWER I...

Page 16: ...for clarity 0 24V 15V 0 15V 230V 400V 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolator L1 E L2 L3 N L1 L2 L3 N T1 T2 T3 N 1 2 3 4 Key Factory Con...

Page 17: ...0V 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolator L1 E L2 L3 N L1 L2 L3 N T1 T2 T3 N 1 2 3 4 Key Factory Connection Customer Connection Mandato...

Page 18: ...Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolator L1 E L2 L3 N L1 L2 L3 N T1 T2 T3 N 1 2 3 4 Key Factory Connection Customer Connection Mandatory Customer Connection Optional FC...

Page 19: ...2 3 4 Key Factory Connection Customer Connection Mandatory Customer Connection Optional FC BUS 100 240V RELAY RELAY RELAY RELAY RELAY CONFIGURABLE COM SHD COM HOT OUT9 NO OCOM9 OUT8 NO OCOM8 OUT7 NO...

Page 20: ...0 240V RELAY RELAY RELAY RELAY RELAY CONFIGURABLE COM SHD COM HOT OUT9 NO OCOM9 OUT8 NO OCOM8 OUT7 NO OCOM7 OCOM6 OUT6 NC OUT5 NC OUT6 NO OUT5 NO OCOM5 OUT4 OCOM4 OUT3 OCOM3 OUT2 OCOM2 OUT1 OCOM1 COM...

Page 21: ...BLE COM SHD COM HOT OUT9 NO OCOM9 OUT8 NO OCOM8 OUT7 NO OCOM7 OCOM6 OUT6 NC OUT5 NC OUT6 NO OUT5 NO OCOM5 OUT4 OCOM4 OUT3 OCOM3 OUT2 OCOM2 OUT1 OCOM1 COM POWER IN8 ICOM8 IN9 ICOM9 IN6 ICOM6 IN7 ICOM7...

Page 22: ...15mins for Room Module PIR s This is in addition to any software run on times 8 3 2 RM 3 Speed Fan Override ESCO TDFS Only When a RM fan speed override is available it will override fan speed function...

Page 23: ...to reduce CO2 concentration The target CO2 sensor setpoint can be changed as one of the commissioning setpoints Room Module CO2 sensors are detected automatically 0 10V CO2 sensors need to be assigne...

Page 24: ...exchanging or bypassing will achieve the same supply temperature 8 14 2 Room Temperature Control While an enable signal is present this mode modulates heating cooling heat exchanger bypass dampers wit...

Page 25: ...r unit The enable run on time must be set to 3 minutes for reverse cycle units This is required in order to keep the compressor running for at least 3 minutes for each period 8 18 Night Cooling Summer...

Page 26: ...X bypass damper is driven to bypass while fans are enabled the indicator will signal open windows HX Bypass due to Condensate pump failure will not affect windows status The Window Mode Status will in...

Page 27: ...utput from a device BV Binary Variable A true false object which exists within a device MSV Multi State Variable This is an enumerated object which can have a number of states each represented by a nu...

Page 28: ...the physical medium BACnet messages are always the same A router can be fitted to the network to translate BACnet between different physical media 8 37 1 Example BACnet Network 21 Example BACnet Netwo...

Page 29: ...of the UI4 input MSV 10209 None 1 None 2 N A 3 N A 4 0 10V CO2 Sensor 5 0 10V Temperature Sensor 6 0 10V Humidity Sensor 7 0 10V Pressure Sensor 2 IN5 The 0 10 voltage at input 5 AI 10035 N A volts 3...

Page 30: ...t Schedule object AV 18215 22 Degrees Celsius 33 T Sens Op Temperature sensor operation MSV 10215 NS Average 1 NS Average 2 Return Air Only 3 NS Return Average 33 0 10v Temp Range Temperature sensor r...

Page 31: ...CO2 Value AV 10265 650 Parts per million 29 0 10 v CO2 Range CO2 sensor output range MSV 10200 N A 1 0 2 000ppm 2 0 4 000ppm 3 0 5 000ppm 4 0 10 000ppm 5 0 20 000ppm 29 CO2 Sensor Op CO2 sensor opera...

Page 32: ...egrees Celsius 4 RM203 Humidity The Humidity at RM address 203 AI 10107 N A Percent Relative Humidity 8 RM203 Setpoint The setpoint at RM address 203 AV 10113 N A Degrees Celsius 5 RM212 CO2 The CO2 a...

Page 33: ...m Unit is latched in critical alarm MSV 15309 N A 1 Normal 2 Alarm 38 Maint Alarm Maintenance Alarm MSV 15310 N A 1 Normal 2 Alarm 38 Sensor Alarm Sensor Out of Range MSV 17009 N A 1 Normal 2 Alarm 39...

Page 34: ...s Ignore all MSTP network PIR sensors MSV 10208 No 1 No 2 Yes 17 EF Max Volt The upper voltage for the extract fan AV 17273 10 Volts 17 EF Start Volt The voltage required to start the extract fan AV 1...

Page 35: ...ade continuous along the bus length Room Modules must not be fitted more than 150metres cable length from the controller 9 5 Touch Screen ESCO LCD Field Advanced Display FAD The ESCO LCD is a user fri...

Page 36: ...y the strategy at priority level 16 By default the ESCO LCD will override these values at priority level 8 Overriding these values is not recommended and may cause undesirable operation Be sure to rel...

Page 37: ...e home page and a security password is set the home page will be locked The only way to exit the target screen in this case is to press the Nuaire logo to the top right of the screen for 5 seconds 28...

Page 38: ...the View Config screen De select the write tickbox all controller points are now read only A service password will need to be set to stop users re enabling the write function 9 7 4 Allow Writing Of Ba...

Page 39: ...he LCD The screen will automatically change to a download screen Select the item required and choose upload To download data to the LCD select the data type and choose download If a user or service pa...

Page 40: ...e Max_Master property of the node s Device object 127 APDU Time The APDU Timeout property defines the amount of time in seconds the FAD waits for responses from other devices 3 9 10 2 Display Settings...

Page 41: ...es are automatically detected and require no set up The majority of RM modules monitor room temperature however options are available to also monitor zone humidity carbon dioxide CO2 local temperature...

Page 42: ...annot change via RM sensors This must be changed through a commissioning tool 10 3 Installation 10 3 1 Removing Rear Cover Use a pozi screwdriver to loosen the screw on the top of the unit Insert a co...

Page 43: ...S 80x80 YES YES YES YES 199 fixed Max of 1 per controller Group 2 Max of 4 Per Controller ESCO TS 80x80 YES 200 203 ESCO THS 80x80 YES YES 200 203 ESCO TDS 80x80 YES YES 200 203 ESCO TDHS 80x80 YES YE...

Page 44: ...nce of 15 ft 4 6m Based on a clear line of sight Ambient Operating Conditions 10 to 30 C 10 to 90 RH Temp Probe 10 to 60 C Ambient Storage Conditions 20 to 60 C t to 95 RH CO2 Sensor Warmup Time Less...

Page 45: ...twisted pair with RJ12 Plugs 26AWG Room Module Room Module RJ12 Plug RJ12 Plug Room Module Sensor SA Bus RJ 12 Modular Jack 6 5 4 3 2 1 Power 15 VDC Power 15 VDC Bus and Power Common Bus and Power Com...

Page 46: ...ve will open whether the fans are running or not This is for pipe freeze protection The LPHW section requires its own supply in order to power the valve actuator 12 2 Wiring LPHW Frost Coil Unit Sizes...

Page 47: ...exact position prior to being removed Disposable filters should be checked and changed when they become fully laden with dust Washable filters should be removed and washed in a mild detergent flushed...

Page 48: ...ge clean if required failure to do so may impair the performance and energy efficiency of this unit Ensure condensate drains are cleaned clear and that water can flow freely from unit Check fin coil b...

Page 49: ...nformation including spare parts and replacement components please contact the After Sales Department If ordering spares please quote the serial number of the unit together with the part number if the...

Page 50: ...te provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to duct work systems They must not be used to support the ductwork 4 4 Local Environment Humidity Am...

Page 51: ...51 30 07 20 Document Number 671760 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS V CO Installation Manual NOTES...

Page 52: ...52 30 07 20 Document Number 671760 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS V CO Installation Manual NOTES...

Reviews: