background image

IMPORTANT — 

This Document is customer property and is to remain with this unit.

Please return to service information pack upon completion of work.

EMI/EFI Air Handler Kit

Model:

BAYAHEMIKIT001A

Used With:

EMI/EFI Air Handler Motor

BAYAHEMIKIT001A KIT COMPONENTS

See Figure 1

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

SERVICE 

INSTALLER'S

GUIDE

APPLICATION:

The EMI/EFI Air Handler Kit may be used on any air handler 
unit with a CTM or variable speed motor. This Kit helps to 
reduce the emitted noise generated when running these 
motors. 

18-GJ84D1-1A-EN

FIGURE 1

s

s

WARNING

!

The cabinet must have an uninterrupted or unbroken 

ground according to National Electrical Code, ANSI/NFPA 

70 - "latest edition" and Canadian Electrical Code, CSA 

C22.1 or local codes to minimize personal injury if an 

electrical fault should occur.

Failure to follow this warning could result in an electrical 

shock, fire, injury, or death.

DISCONNECT POWER BEFORE SERVICING

WARNING

EMI Kit BAYAHEMIKIT001A

ITEM # Part Number

Part Description

Qty

1

D806151

TEM Male/Female Harness

1

2

D806153

TAM / GAM 
Male/Female Harness

1

3

D806180P01

In-line EMI Filter (Schaffner)

1

4

D806121P01

Bracket, In-line EMI Filter

1

5

D804964P08

Gasket for back of Bracket

1

6

D806181P01

Ferrite Beads

2

7

D905103P01

#10 x 3/8" Cutting Screws

2

8

D804271P01

#8 x 1/2" Screws

2

9

D803499P01

#8 x 1/2 Cutting Screws

2

10

C107736P07

Cable Ties

4

11

18-GJ84D1-1A-EN Installation Instructions

1

12

D806182P01

Wiring Diagram

1

13

D806182P02

Wiring Diagram

1

14

D806182P03

Wiring Diagram

1

s

s

WARNING

!

 

Disconnect power to the unit before removing the blower  

or coil door.

Failure to follow this warning could result in personal in-

jury from moving parts.

1

2

3

4

5

6

7
8
9

10

s

s

WARNING

!

Prevent all wires from touching any hot surfaces.

Failure to follow this warning could result in dangerous 

operation, serious injury, death or property damage.

Summary of Contents for BAYAHEMIKIT001A

Page 1: ...llow this warning could result in an electrical shock fire injury or death DISCONNECT POWER BEFORE SERVICING WARNING EMI Kit BAYAHEMIKIT001A ITEM Part Number Part Description Qty 1 D806151 TEM Male Fe...

Page 2: ...ing two 10 cutting screws Item 7 NOTE Make sure to align the left edge of the bracket with the left edge of the blower housing See Figure 4 4 Installing Ferrite Bead Item 6 on a variable speed motor P...

Page 3: ...cut to have enough wire to make the loops FIGURE 6 FIGURE 7 7 Disconnect the 3 pin connector between the blower motor and the power supply Pull the harness out of the blower deck slot and back in fro...

Page 4: ...d side 9 Make sure the new harness is secured in the blower slot Connect the male 3 pin connectors to the power supply above the blower in the coil cabinet Connect the female 3 pin connector from the...

Page 5: ...res pass through the ferrite bead twice See Figure 14 FIGURE 14 FIGURE 13 FIGURE 15 FIGURE 16 4 Installing Ferrite Beads Item 6 on a CTM motor Place one ferrite bead on motor power wires There should...

Page 6: ...s at the wire nut 7 Connect the incoming power wires to the line side of the EMI filter See Figure 17 8 Connect the 2 wire unit harness to the load side of the EMI filter See Figure 17 FIGURE 17 9 Use...

Page 7: ...es pass through the ferrite bead twice See Figure 20 FIGURE 20 FIGURE 19 FIGURE 21 FIGURE 22 4 Installing Ferrite Beads Item 6 on a CTM motor Place one ferrite bead on motor power wires There should b...

Page 8: ...between the line heater power and the unit controls 8 Take the male 6 pin connector and plug it into the EMI filter harness female connector on the line side See Figure 24 9 Take the female 6 pin conn...

Page 9: ...Page 9 FIGURE 26 Wiring Diagrams D806182P01 D806182P02 NOTE Place the appropriate EMI kit wiring diagram label next to the existing wiring diagram on the unit for future reference...

Page 10: ...on please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice W...

Reviews: