EMI FILTER INSTALL INSTRUCTIONS FOR
TEM AIR HANDLERS WITHOUT HEATERS
1. Locate the EMI Filter (Item 3) on the left side of the
heater barrier. See Figure 13.
2. Use the two included #8 cutting screws (Item 9) to
mount the EMI filter in place.
3. Installing Ferrite Bead (Item 6) on a variable speed
motor.
Place one ferrite bead on motor power wires.
There should be at least one loop made in the power
wires, so the wires pass through the ferrite bead twice.
See Figure 14
FIGURE 14
FIGURE 13
FIGURE 15
FIGURE 16
4. Installing Ferrite Beads (Item 6) on a CTM motor.
Place
one ferrite bead on motor power wires. There should be
at least one loop made in the power wires, so the wires
pass through the ferrite bead twice. See Figures 15
and 16.
NOTE: The black tape wrap may need to be cut to have
enough wire to make the loops.
5. For units with a CTM motor, place a second ferrite bead
on the low voltage wires. There should be at least one
loop made in the low voltage wires, so the wires pass
through the ferrite bead twice. See Figure 16.