background image

19

19

GB

Menu stage 4: Setting / adjusting the bottom

end-of-travel position

Wait a short while until “4” starts flashing.
Press button

. The operator causes the door to

travel in the CLOSE direction as long as the button is
pressed. The position can be altered to the OPEN
direction via button ..
Once the desired CLOSE end-of-travel position has
been reached, press button

. The operator stores

the CLOSE end-of-travel position and “5” appears in
the display.
Press button

twice until “0” appears.

During this opening and closing cycle, the

operator learns the force required to open and close
the door.

The cycles

must not be interrupted. During these cycles must
not be interrupted. During these cycles “0” appears
in the display.

- Press button

. The operator causes the door to

open until the top end-of-travel position has been
reached.

- Now press button

again. The operator causes

the door to close until the bottom end-of-travel
position has been reached.

- After approx. 2 seconds, “0”disappears.

If you have previously quit the setting menu, press
button

for 3 seconds until “3” appears. Then press

button

twice until “5” appears.

After approx. 2 seconds, the display flashes showing
the set value of the opening force limit. The force limit
setting can be increased or decreased via buttons

and . After setting the value, press button

. “6”

is displayed.

After approx. 2 seconds, the display starts flashing,
and the set value for the closing force limit is
displayed.
The force limit setting can be increased or decreased
via buttons

and .

After setting the value, press button

. “0” appears

in the display.
Finally, check the force settings, and, if necessary,
repeat the setting procedure.

If the force setting is too high, persons may

be placed at risk of injury.
The factory setting is 4!

- Place an obstruction (e. g. operator’s cardboard

box) underneath the doors’s closing edge.

- Starting from the OPEN end-of-travel position,

actuate the door to close.

- The door travels towards the obstruction,

If the door springs have been changed or altered, then
the force learning cycle must be repeated: Proceed to
menu stage 5 and keep button

pressed for 3

seconds. “0” appears in the display. Then complete
the force learning cycle as explained under point 14.

Force-learning cycle

Attention:

Menu stage 5: The opening force limit

Menu stage 6: The closing force limit

Caution!

Checking the force limit facility

stops

and travels back.

A force limit does not apply!

13

14

15

• Operating Instructions

Pull the mains plug before starting to work!
All persons using the gate system must be
shown how to operate it properly and safely:
When the operator is being used, the opening
and closing phases must be monitored.
Keep hand transmitters out of the reach of
children.
It must be ensured that neither persons nor
objects are located in the gate’s way of travel.

Functional sequence

• Internal safety device

• Quick release

• Lighting

• Hand transmitter

The garage door operator can be actuated by an
impulse generator such as hand transmitter, key
switch etc. It is only necessary to generate a short,
sharp impulse.

Operator starts up and causes the door to travel to
set open or closed travel limits.

The door stops.

Door continues to move but in opposite direction.

If the closing door encounters an obstruction, the
operator stops and causes the door to open to its top
end-of-travel position in order to clear the
obstruction.
During the last 2 seconds of the closing cycle, the
door only opens slightly, this being sufficient to clear
the obstruction but otherwise preventing anyone
from taking a look into the garage.
If the opening door encounters an obstruction, the
operator stops immediately and can be closed by
generating another impulse.

During adjustments, in the event of a power failure or
malfunctions, the door can be disengaged from the
operator by actuating the pull cord on the carriage
and then be operated manually.
If the door is to be operated manually over a longer
period of time, then the existing locking pin must be
inserted (see figure 8). The door latches put out of
service for power operation must be refitted,
otherwise the door is not latched in the the closed
position.
In order to restore power operation, return the
locking pin to the parking position (a) and put the
latches out of service.
After an impulse has been generated, the door
automatically latches with the door operator.

The lighting switches on automatically whenever a
start impulse is generated and switches off again
after the set time phase (factory setting approx. 90
seconds).

Changing the bulb: Slide back the cover and change
the bulb (230V, 40W, socket E14). Slide the cover
back on.

Programming further hand transmitters: see image
11.

First impulse:

Impulse generated while door is moving:

Repeated impulse:

• Maintenance / Checks

The door system must be inspected
and tested by a specialist company
prior to initial operation and at least
once a year thereafter.

Monitoring the force limit

Caution!

The operator control unit features a dual-processor
safety system to monitor the force limit.
The integral force cut-out is automatically tested at
each travel limit.
The door system must be checked prior to initial
operation and at least once a year thereafter. In the
process, the force limiting device (figure 16) must be
tested!

If the closing force is set too

high, persons can be placed at risk of
injury or property could sustain damage.

The force limit for the opening cycle can be adjusted
in menu stage 5, the force limit for the closing cycle
can be adjusted in menu stage 6.

The cycle counters stores the number of opening or
closing cycles performed by the operator.

In order to read out the meter, keep the
button

pressed for 3 seconds until a number is

displayed. The display throws out the values
beginning from the highest decimal place down to
the lowest one after another. In the end, a horizontal
line is displayed. Example: 3456 cycles, 3 4 5 6 -

• Cycle counter

Retain these installation, operating and maintenance instructions for the full duration of the operator’s service life!

Summary of Contents for Novomatic 200

Page 1: ...WN 020955 04 11 Novomatic 200...

Page 2: ...13 2 3 3 11 10 13 14 9 4 6 2 1 7 5 8 12 17 16 D A B H E C F A 3260 mm F 0 100 mm G 30 50 H 130 mm B 2560 mm C 2960 mm D 3080 mm E 30mm G 0 1 2 1 2 3 3a...

Page 3: ...1 2 3 4 3b 1 2 3 4 5 6 3c door 1 2 3d...

Page 4: ...door click 1 2 3 3e 1 2 1 cm 3f 1 2 4a...

Page 5: ...1 2 X a 5 1 2 4b 6a 1 2 6b...

Page 6: ...F E E a b a 8 9 1 2 max 50 7c 3400 mm 2x 1500m 11 11 iso 20 17 7b 7a 9a F 9b...

Page 7: ...3 sec 3x 13 F F 400N 50mm 15 12 1 2 3 14 2 2 1 1 2 3 5x 2 sec 11 A a C B D 10 1 2 3...

Page 8: ...conformit CE NL EU Verklaring van conformiteit E Declaraci n de conformidad de la UE PL PT Declara o de conformidade CE HR Izjava o usugla enosti sa normama Evropske unije SL EU Izjava o skladnosti D...

Page 9: ...odukt arbeitet mit hoher elektrischer Spannung Vor Beginn der Arbeiten an elektrischen Anlagen ist folgendes zu beachten 1 Freischalten 2 Gegen Wiedereinschalten sichern 3 Spannungsfreiheit feststelle...

Page 10: ...Kettenritzel 3 Laufschiene Antriebsseite 4 Laufschlitten 5 Kette 6 Umlenkrolle 7 Verbindungsst ck 8 Laufschiene Torseite 9 Spannvorrichtung 10 Wandbefestigung 11 Schubstange 12 Schraubenbeutel 13 Dec...

Page 11: ...rscheint Bei dieser Auf und Zufahrt lernt der Antrieb die Kraftkurven ein und ist Die Fahrten d rfen nicht unterbrochen werden Die Anzeige zeigt w hrend dieser Fahrten die Ziffer 0 an 1 Bet tigen Sie...

Page 12: ...ern oder neu liefern F r Sch den infolge mangelhafter Einbau und Montagearbeiten fehlerhafter Inbetriebsetzung nicht ordnungsgem er Bedienung und Wartung nicht sachgerechter Beanspruchung sowie jeglic...

Page 13: ...rische Leitungen Zustand ________________________ 3 3 Schnell Notentriegelung Zustand Funktion ________________________ 3 4 Bet tigungseinrichtungen Zustand Funktion ________________________ 3 5 Endab...

Page 14: ...ermitteln Konform ist mit den Bestimmungen der EG Bauproduktenrichtlinie 89 106 EG F r den Teil Betriebskr fte wurden die entsprechenden Erstpr fungen in Zusammenarbeit mit den anerkannten Pr fstellen...

Page 15: ...nale y przestrzega nast puj cych punkt w czy od napi cia y przed ponownym za czeniem Upewni si o braku napi cia zez wykwalifikowanego elektryka rzestrzeganiu na unikn t odszkodowawcze wobec producent...

Page 16: ...hwytu ciennego Wiertarka do metalu Klucz 13 mm 3 mm 2 x 100 Poziomica Szczypce i stosownie do warunk w budowlanych 1 wraz z 40W i E 27 2 K 3 Szyna od strony 4 W zek 5 6 zwrotny 7 Profil 8 Szyna od str...

Page 17: ...zamyka si kra cowy oko o wy wietlacz Je li opu cili my wcze niej menu stawie wcisn przez 3 sekundy przycisk a do pojawienia si cyfry 3 na wy wietlaczu Nast pnie dwukrotnie wcisn przycisk a do pojawien...

Page 18: ...ie tego cyklu nap d pracuje z maksymalna si Sprawdzi bram pod k ma zbyt du e opory ruchu cyfra 0 znika Brama nie otwiera ani nie zamyka Brama nie zamyka si na etapie menu nr 3 mpuls przy starcie przy...

Page 19: ...________________________ Przewody elektryczne przy cza Stan 3 3 ________________________ Odblokowanie awaryjne Stan funkcjonowanie 3 3 1 ________________________ Szybki a cuch Stan funkcjonowanie 3 3...

Page 20: ...STOP A PL C Wej cie STOP B Wej cie STOP C Kat Zastosowane zosta y przy tym normy zharmonizowane EN12978 EN13849 1 oraz EN60335 1 Sporz dzone zosta y techniczne podk adki dokumentacyjne wed ug za czni...

Page 21: ...bserve the safety advice and information provided in these Operating Instructions as well as the accident prevention and general safety requirements relevant to the field of application shall exempt t...

Page 22: ...ensioner 10 Wall bracket 11 Linking bar 12 Bag of screws 13 Support straps 13 Hand transmitter 14 Internal push button Build together the track as shown in images 3a and 3f Positioning the prefitted o...

Page 23: ...r can be actuated by an impulse generator such as hand transmitter key switch etc It is only necessary to generate a short sharp impulse Operator starts up and causes the door to travel to set open or...

Page 24: ...l safety device has been activated e g Photocell Motor does not rotate Call in a specialist company Door no longer accepts a start impulse External impulse generator emits a permanent impulse signal e...

Page 25: ...___ Manual operation of the door Smooth running 1 2 ________________________ Fastenings connections State Seat 1 3 ________________________ Pivots joints State Lubrication 1 4 ________________________...

Page 26: ...f control systems Integrated force limit kat 2 PL C In doing so the harmonized standards EN13849 1 were applied The technical documents in accordance with annex VII B were drawn up Conformity is in ac...

Page 27: ...tilisation concern ainsi que des consignes g n rales de s curit Le produit a t soumis une analyse de risques Bas es sur cette analyse la conception et la r alisation du produit r pondent l tat actuel...

Page 28: ...au plafond 10 Remarque Liaison Console de jonction de la porte Chariot 11 4 Orientation de l antenne Sch ma de connexion Remarques D verrouillage du chariot 4 Remarque a b a 9 Pour effectuer d autres...

Page 29: ...rs la position finale OUVERTURE ou FERMETURE programm e la porte s arr te la porte inverse sa man uvre et continue dans le sens contraire Si la porte rencontre un obstacle en fermeture la motorisation...

Page 30: ...normal Le raccordement STOP A est coup Le dispositif externe de s curit a r agi ex Portillon Le raccordement STOP B est coup Le dispositif externe de s curit a r agi ex Barrage photo lectrique Le mot...

Page 31: ...e rotation l ments articul s Etat Graissage 1 4 ________________________ Galet support de galet Etat Graissage 1 5 ________________________ Joints barres de contact Etat Assise 1 6 ___________________...

Page 32: ...e EN12978 Les documents techniques ont t cr s selon l Annexe VII B Elle est conforme aux dispositions correspondantes de la directive CE concernant les produits de onstruction 89 106 CEE Pour la parti...

Reviews: