background image

- 6 - 

RNPP-311M

  

                                                                                                                       

NOVATEK-ELECTRO

 

U

max

 

– voltage is higher than the user adjusted value of 

U

max 

The  switches 

SEQ,  IMB,  Umin,  Umin 

are  intended  for  permission  /  prohibition  of  relay  operation  in 

case of 

emergency.

 

If the switch is set to the Left position 

– then the corresponding function is turned 

ON

;  

If the switch is set to the Right position 

– this function is disabled. 

RNPP-311M will operate by 

any one of 

SEQ, IMB, U

min

, U

min 

emergency

 if

 

this switch is set to the Left 

position (ON).

 

 

4. START UP PROCEDURE AND OPERATION 

 

4.1 RNPP-311M 

is supplied ready to use and doesn’t require any special start up procedures. Due to 

the  use  of  microprocessor  based  scheme  all  the  settings  and  adjustments  are  set  precisely  accurately  and 
there is no need to check the accuracy of settings with a help of testing voltmeter. 

After long time storage period it is recommended to check the functionality of RNPP-311M. There is no 

need to perform any routine maintenance if the RNPP-311M is already in use for a long time and being used 
in accordance to the operation conditions stated in the present documentation. 

 

ATTENTION!

 

  All  the  terminals  connections  and  operation  should  be  strictly  performed  according  to 

safety regulations. It is recommended to adjust all the knobs and select necessary functions when the  
RNPP-311M 

is in the “cold” state (not energized). When testing the device it is allowed to make adjustments 

and change the settings on the energized RNPP-311M.

 

 

4.2 Start up procedure:

 

1. Using adjustment knobs set the required values of voltage tripping thresholds 

U

nom

±%

; tripping time 

delay 

T

off

 and autoreclosing time delay 

T

on

2. Using 5-8 switches on the front panel (Figure 1) at the left or right position.  
Left position of the switch - function is enabled;  

Right position 

–function disabled. 

3. With the use of the DIP switch 4 ( Figure 1) set the type of the power supply input.  
4. Connect  RNPP-311M  in  parallel  to  the  power  load  -  using  input  terminals 

9

10

11

 (see  Figure 1) 

and Neutral to terminal 

12

.  

If necessary connect external 24V (AC/DC) power supply source to terminals 

7

 (

+

) and 

8

 (

); 

5. Connect  output  terminals  (

1-2

(

4-5

)  and 

5-6

(

2-3

))  to  the  control  circuit  (operational  contacts  of  the 

contactor); 

6. Give the power supply to input terminals (energize the RNPP-311M) 

 

If on the first start up RNPP-311M 

doesn’t allow to turn 

ON

 the power load and indicates wrong phase 

sequence alarm but the user is absolutely sure that the phase sequence is correct 

– then it is necessary to 

exchange the wires connected to terminals 

10

 and 

11

If RNPP-311M is being used as a 

maximal voltage protection relay 

then the

 break in the magnetic 

starter coil power circuit 

should be connected to terminals 

1-2

 (

4-5

) (

the reverse logic of switching-on)

.  

The switch 

U

max

 should be set to ON position (enabled)

 and the 

switches 

SEQ

IMB

 and 

U

min

 should 

be set to the OFF position (disabled). 

 

4.3  RNPP-311M usage examples  

 

a)

 Minimal voltage relay 

-  Switch 

Umin

 is set to the left position (function is enabled) 

-  Switches 

Umax

IMB

 are set to the right position (

function disabled)

 

If the voltage level is lower than the user adjusted minimal voltage threshold (

U

nom±%

)

 

– then  

RNPP-311M will turn 

OFF

 the power load with the user preset time delay 

T

off

 and red 

ALARM

 LED indicator 

will  turn  ON.  Corresponding 

LINE

  green  LED  indicator(s)  will  turn 

OFF

  indicating  on  which  line  the  problem 

occurred. If the voltage on any of the lines is lower than 100V 

– then RNPP-311M will turn 

OFF

 the power load 

within 0,2 sec. 

 

b) 

Voltage level monitoring and phase presence control relay 

-  Switches 

U

min

 and 

U

max

 are set to the left position 

If voltage level is higher than the user adjusted maximal voltage threshold (

U

nom±%

– then  

RNPP-311M will turn 

OFF

 the power load with the user preset time delay 

T

off

; in case the minimal voltage 

problem  detected  then  the  power  load  will  be  turned 

OFF

  with  the  fixed  time  delay  of  12  sec  (in  order  to 

escape from fault tripping due to startup voltage drops). Red 

ALARM

 LED indicator will turn 

ON

.  

In case the phase loss detected

– then RNPP-311M will turn 

OFF

 the power load within 0.2 sec. 

 

Summary of Contents for RNPP-311M

Page 1: ...ompounds for cleaning spirit gasoline solvents etc NEVER ATTEMPT TO REMOVE AND REPAIR THE UNIT Some of the unit components may be live NEVER ATTEMPT TO OPERATE THE UNIT WITH THE MECHANICAL DAMAG THE H...

Page 2: ...on each phase Using toggle switch Figure 1 point 4 RNPP 311M user may select the type of the power circuit 400V or 415V and the set of optionally performed functions using toggle switches 5 8 shown o...

Page 3: ...r phase imbalance measurement not more 2 Protection class against electric shock II Permissible contamination level II Overvoltage category II Nominal voltage of isolation V 450 Operational voltage ra...

Page 4: ...ith isolated Neutral then the measurement accuracy for the phase imbalance and voltage tripping thresholds increase to 5 To terminals 7 8 it is possible to connect 24V AC DC external power supply sour...

Page 5: ...on one of phases and the external power supply of 24 V is absent then RNPP 311M saves operability when voltage at least 140 V 3 3 Adjustments and settings ATTENTION Not to break or turn the knobs plea...

Page 6: ...put terminals 9 10 11 see Figure 1 and Neutral to terminal 12 If necessary connect external 24V AC DC power supply source to terminals 7 and 8 5 Connect output terminals 1 2 4 5 and 5 6 2 3 to the con...

Page 7: ...ion against the phases distortion is carried out by a switch IMB In case the phase loss detected or the voltage on any of the lines becomes lower than 100V then RNPP 311M will turn OFF the power load...

Page 8: ...pair damage is caused by electric current or voltage in excess to the permissible values as indicated in the Operating manual 6 4 Warranty service is provided in the place of purchase 6 5 Post warrant...