- 5 - 

NOVATEK-ELECTRO

                                                                                                 RNPP-311M

  

                                                                                                                       

 

Green LED 

indicators LINE 

Indication status 

LINE 

Red LED ALARM 

Indication status 

ALARM 

Functional state  

of RNPP-311M 

 

All LEDs are 

permanently 

ON

 

 

Luminescence

 

is absent 

Voltage parameters 

on each phase are 
normal.  

 

 

 

Blinking (reverse 

reading of the  
autoreclosing time 
delay  

 

Blinking of any (all) 

LEDs 

 

Continuous 

luminescence  

Voltage rise on the 

corresponding phase 
is detected 

 

Any (all) LEDs are 

OFF

  

 

Continuous 
luminescence 

1) Voltage level on any 
(all) of phases is lower 
than the user adjusted 
value; 

2) Voltage level on 

any (all) of phases is 
lower than 100V or the 
phase loss is detected; 

 

Blinking of two 

LEDs alternately. At 
first Middle and 
Right LEDs turn 

ON

 

and then Middle and 
Left turn 

ON

 

 

Continuous 
luminescence 

Phase imbalance 

alarm situation. 

 

Left, Middle and 

then Right LEDs turn 

ON

 one by one 

 

Continuous 
luminescence 

Wrong phase 

sequence and phase 
coincidence alarm 
situation 

 

NOTE -

  

If several alarm situations happen concurrently then they are indicated according the following 

priority: 

– Phase loss or voltage level on any of phases decrease lower than 100V (the highest precedence); 

– Wrong phase Sequence; 

U

min

 and 

U

max

– Phase imbalance alarm. 

 

If the voltage is present only on one of phases and the external power supply of 24 V is  absent then 

RNPP-311M saves 

operability

 when voltage at least 140 V. 

 

3.3. Adjustments and settings 

 

ATTENTION

!  Not  to  break  or  turn  the  knobs,  please,  don't  make  excessive  efforts  when  performing 

adjusting operations. 

 

On  the front  panel  of  the  RNPP-311M  there  are  3  adjustment knobs to  set  the  desired  values  and  5 

switches to select necessary modes of operation (see Figure 1): 

U

nom±%

  -  combined  adjustment  for  the  minimal/maximal  voltage  tripping  thresholds  in  %  of  nominal 

(rated) voltage; 

T

off

 

–  tripping  time  delay  setting  (in  seconds)  for  all  alarm  situations  except  the  phase  loss  or  if  the

 

voltage on any of the phases gets lower then 100V. It is recommended to set the 

T

off

 time not less than  

1 sec to escape from undesired frequent trippings caused by fluctuations in power circuits; 

T

on

 

– time delay (in seconds) for automatic turn 

ON

 of the power  load  when the  voltage parameters 

returned  back  to  normal  values  after  the  detected  voltage  interruption  (autoreclosing  time  delay);  turn 

ON

 

time delay for after correct voltage is applied to the input terminals; 

 

3.4 Toggle switches 4 

– 8 

(see Figure 1):

 

Using the switches user may select necessary functions for RNPP-311M to perform: 

400/415V

 

– to select the desired standard of the power circuit; 

SEQ

 

– wrong phase sequence or phase coincidence; 

IMB

 

– phase imbalance; 

U

min

 

– voltage is lower than the user adjusted value of 

U

min

Summary of Contents for RNPP-311M

Page 1: ...ompounds for cleaning spirit gasoline solvents etc NEVER ATTEMPT TO REMOVE AND REPAIR THE UNIT Some of the unit components may be live NEVER ATTEMPT TO OPERATE THE UNIT WITH THE MECHANICAL DAMAG THE H...

Page 2: ...on each phase Using toggle switch Figure 1 point 4 RNPP 311M user may select the type of the power circuit 400V or 415V and the set of optionally performed functions using toggle switches 5 8 shown o...

Page 3: ...r phase imbalance measurement not more 2 Protection class against electric shock II Permissible contamination level II Overvoltage category II Nominal voltage of isolation V 450 Operational voltage ra...

Page 4: ...ith isolated Neutral then the measurement accuracy for the phase imbalance and voltage tripping thresholds increase to 5 To terminals 7 8 it is possible to connect 24V AC DC external power supply sour...

Page 5: ...on one of phases and the external power supply of 24 V is absent then RNPP 311M saves operability when voltage at least 140 V 3 3 Adjustments and settings ATTENTION Not to break or turn the knobs plea...

Page 6: ...put terminals 9 10 11 see Figure 1 and Neutral to terminal 12 If necessary connect external 24V AC DC power supply source to terminals 7 and 8 5 Connect output terminals 1 2 4 5 and 5 6 2 3 to the con...

Page 7: ...ion against the phases distortion is carried out by a switch IMB In case the phase loss detected or the voltage on any of the lines becomes lower than 100V then RNPP 311M will turn OFF the power load...

Page 8: ...pair damage is caused by electric current or voltage in excess to the permissible values as indicated in the Operating manual 6 4 Warranty service is provided in the place of purchase 6 5 Post warrant...