Primary Number Communication Format (16)
One location is needed to select the Communication Format to the primary phone number. Address 16 is
used for this purpose. The default (factory setting) for this address is Contact ID, which is 4+2 Standard,
1800 Hz 'Carrier', 2300 Hz 'ack'. You may enter 0, 1, 2, 4, 6, 8, C or E in place of the default, then press
ENTER
/
STORE
. When selecting the format, note that Ademco Contact ID is the only format in the
UDACT which identifies the specific zone or point status to the Central Station. All other formats report
the number of zones or points that are active but do not identify the specific zone or point. Choose
from the list of formats below:
Note:
Consult your Central Station for proper selection or consult our factory representatives. For any format chosen,
the UDACT automatically programs all of the event codes. See Table 4 through Table 9.
CAUTION:
Default entries for event codes are always programmed into memory when
ENTER
/
STORE
is pressed at this location! This can be avoided by using the up or down arrows to navigate through
programming locations.
Primary Number Account Code (17-20)
Four locations at addresses 17-20 default to all '0's. Valid entries are (0-9 and A-F). The number of
digits entered must match the format selection. If programming '2 or 4' into address 16, enter 3 digits
(location 20 is ignored). If programming '0, 1, 6, 8, A, C, or E' into address 16, enter 4 digits.
Primary Number 24 Hour Test Time (21-24)
Use military time when entering the 24 hour Test Time. The 24 hour test report to phone number 1 takes
up four locations, from addresses 21-24. The default is 00:00 (12:00 midnight). The limits for each
location are as follows; 21: enter 0, 1 or 2; 22: enter 0-9; 23: enter 0-5; 24: enter 0-9.
Note:
Do not use A-F.
0:
4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
1:
4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2:
3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3:
Not Used
4:
3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5:
Not Used
6;
4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7:
Not Used
8:
4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9:
Not Used
A:
4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B:
Not Used
C:
4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D:
Not Used
E:
Ademco Contact ID (default)
F:
Not Used
!