Ademco Contact ID Format
42
UDACT Instruction Manual PN 50050:H 09/16/2002
Secondary Number
If 'E' is entered for address 42, the following data is automatically programmed for the secondary phone number
event codes.
Enter a '000' for the data setting to disable the report.
Table 9 Ademco Contact ID, Secondary Number
Notes:
1) Zero entries prevent the transmission of the report to the Central Station.
2) Refer to Contact ID program locations 64 - 68.
3) The identification of the zone/device number is automatically transmitted by the UDACT and is added to the main
event code. See Table 5-3 for more information.
4) For control panels; System 500, System 5000, AFP-200, AFP-400, AFC-600, NFS-640, AFP1010, AM2020, INA,
NFS-3030, and NCA the factory default event code is 110 and reprogrammable. The AFP-400 and AFP-100 are
unique in point reporting mode in that only the control module report codes are programmable. The factory setting of
report code 111 is fixed for addressable smoke detectors and cannot be changed.
5) AFP-200 applications transmit by zone, not by point.
6) The Group # is automatically incremented for AM2020/AFP1010/INA applications.
Address
Description
Setting
1
Group #
6
Sensor #
139-141
Secondary# General Alarm Code
110
00
000
2
142-144
Secondary # Zone/Point Alarm Code
5
110
4
00
Note
3
145-147
Secondary # General Supervisory Code
200
00
000
2
148-150
Secondary # Zone/Point Supervisory Code
5
200
00
Note
3
151-153
Secondary # General Fault Code
300
00
154-156
Secondary # AC Fault Code
301
00
157-159
Secondary # Zone/Point Fault Code
5
380
00
Note
3
160-162
Secondary # Low Battery Fault Code
302
00
163-165
Secondary # Telco Primary Line Fault Code
351
00
166-168
Secondary # Telco Secondary Line Fault Code
352
00
169-171
Secondary # NAC Fault Code
321
00
172-174
Secondary # Comm. Trouble Primary # Code
354
00
175-177
Secondary # Comm. Trouble Secondary # Code
354
00
178-180
Secondary # 485 Comm. Trouble Code
300
00
181-183
Secondary # System Off Normal Code
308
00
184-186
Secondary # UDACT Off Normal Code
350
00
187-189
Secondary # System 24 Hour Test
602
00
190-192
Secondary # System 24 Hour Test w/active event
608
00
193-195
Secondary # Manual Test Message
601
00