Modes and Special Functions
UDACT Instruction Manual PN 50050:H 09/16/2002
15
Modes and Special Functions
Normal Mode
Normal Mode is the standard mode of operation. In this mode, the UDACT
monitors host FACP status as well as monitoring telephone line voltage. The
UDACT reports system status information to UL listed Central Stations.
Information transmitted includes general alarm, trouble and supervisory. It
also transmits either the number of zones or points activated or the specific
point(s) activated, depending upon the compatible panel, programming
selections and transmission format selection. Specific system trouble
conditions and specific UDACT troubles are also transmitted.
Program Mode
Program Mode is used to program the UDACT. While the UDACT is in the
program mode, it cannot receive host FACP status information. Refer to
“Programming Instructions” on page 29 for complete information.
Type Mode
Type Mode is used to define the specific type of device (point) used or
function of a zone. Type Mode is also used to disable the alarm report for any
zone/point in the system.
Note:
AM2020/AFP1010, NFS-3030, INA, AFC-600, NFS-640, and NCA applications
restrict Type Mode programming to a maximum of 568 points. All remaining points
above 568 will report as fire alarm points only.
Troubleshoot Mode
Troubleshoot Mode may be used for testing the telephone line wiring.
Connection from the UDACT's modular jacks, through RJ31X jacks and into
the telephone network may be easily checked. In this mode, the keypad acts
similar to a telephone touchpad.
Lamp Test Mode
Lamp Test mode turns on all segments of the 4 character display plus all
LEDs on the UDACT, except primary and secondary LEDs.