Programming Options
32
UDACT Instruction Manual PN 50050:H 09/16/2002
Primary Number 24/12 Hour Test Time Interval (25)
The test report sent to the primary phone number may be sent every 12 or 24 hours. If the message is to
be sent every 24 hours, leave the factory default entry of zero. If 12 hour test report time is needed,
enter 1.
Secondary Phone Number (26-41)
Programming
is similar to programming the primary phone number located at addresses 00 - 15. The
defaults are also all 'F's.:
Secondary Number Communication Format (42)
Programming is the same as the primary number's Communication Format at address 16. Default entry
is 'E', Contact ID. When selecting the format, note that Ademco Contact ID is the only format in the
UDACT which identifies the specific zone or point status to the Central Station. All other formats report
the number of zones or points that are active but do not identify the specific zone or point. Choose one
entry from the list below:
CAUTION:
Default entries for event codes are always programmed into memory when
ENTER
/
STORE
is pressed at this location! This can be avoided by using the up or down arrows to navigate through
programming locations.
Secondary Number Account Code (43-46)
This code is programmed in addresses 43 - 46 in the same manner as the primary phone number
Account Code. Default entries are all '0s'.
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
0:
4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
1:
4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2:
3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3:
Not Used
4:
3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5:
Not Used
6;
4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7:
Not Used
8:
4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9:
Not Used
A:
4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B:
Not Used
C:
4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D:
Not Used
E:
Ademco Contact ID (default)
F:
Not Used
!