7-38
Technical specifications
Optical Multiservice Edge 6130 NT6Q92MA Rel 1.0 Iss 1 Standard September 2006
Power and grounding specifications
The following section outlines the power and grounding specifications
DC input voltage range
The operational input voltage range for the OME6130 is -40 V dc to -57.5 V
dc with DC feed. The OME6130 is not damaged when an input voltage of
correct polarity, with a value between zero and -40 V dc (minimum voltage),
is applied for any period of time. The system is not damaged by a reversed
polarity voltage supply, for example, zero to +57.5 V dc (the system does not
function with a reversed polarity supply).
The OME6130 automatically recovers when the input voltage returns to a
value exceeding the minimum voltage within an acceptable period of time and
without any manual intervention.
The OME6130 meets the specifications listed in
.
Table 7-36
Power, grounding, and noise references
Topic
References
Power
• ANSI T1.315-2001, Voltage Levels for DC Powered Equipment
Used in the Telecommunications Environment, 2001.
• ETS 300 132-2, Equipment Engineering (EE); Power supply
interface at the input to telecommunications equipment; Part 2:
Operated by direct current (dc)
• DS8171, Issue 2, 60 Hz and -48 V dc Power for DC Powered
Telecommunication Equipment, Bell Canada
Grounding
• ITU-T K.27, Bonding Configurations and Earthing Inside a
Telecommunication Building), May 1996
• TR-NWT-000295, Bellcore Technical Reference, Isolated Ground
Planes: Definition and Application to Telephone Central Offices.
July 1992
• ETSI EN 300 253, Equipment Engineering (EE); Earthing and
bonding of telecommunication equipment in telecommunication
centres, January 1995
• NFPA70, (US National Electrical Code)
• CSA 22.1, (Canadian Electrical Code)
• Telecordia: GR-1089-CORE, Electromagnetic Compatibility and
Electrical Safety, Issue 2, Revision 1, February 1999, Section 9
Summary of Contents for Optical Multiservice Edge 6130