RetroFit Refill System with Nordson Level Sensor
A-11
Part 1121938_02
2013
Nordson Corporation
Fill Enable LED/Yellow Status LED/Yellow Light Tower
The table below lists the diagnostic warning (yellow flashes) messages for
the STATUS LED (DS3, located on Refill PCA). These flash codes are also
shown on the FILL ENABLE LED located on the membrane panel.
Number of
Yellow
Flashes
(DS3) and
Panel
Enable LED
Diagnostic
Action Required
1
Pressure switch open (if used).
Check air supply to pressure switch. If air
supply good, replace pressure switch.
Check jumper if pressure switch not
used.
2
Lid switch open (if used).
Replace or realign lid switch, if used.
Check jumper if not used.
3
RTD open. Unit will still function, but probe
temperature compensation will be disabled.
Replace sensor
4
Sensor is disconnected.
Reconnect or tighten sensor connector.
If persists, recalibrate the sensor. If still
persists, replace sensor.
5
Melter ready input open (if used)
This is normal during melter warm up. If
occurs while melter is ready, check
connections to input. If melter ready
signal not used, check jumper.
6
Unstable sensor readings
Check the sensor cable connections. If
the problem persists, replace the sensor
and/or refill PCA.
7
Probe temperature is under 175
F
(80
C)) and filling is prevented.
Allow probe to heat above 175
F
(80
C)
Summary of Contents for Mesa Fulfill
Page 46: ...Fulfill Retrofit for Mesa Melters 42 Part 1121938_02 2013 Nordson Corporation Wiring Diagram...
Page 47: ...Fulfill Retrofit for Mesa Melters 43 Part 1121938_02 2013 Nordson Corporation Dimensions...
Page 48: ...Fulfill Retrofit for Mesa Melters 44 Part 1121938_02 2013 Nordson Corporation...
Page 64: ......
Page 65: ......
Page 66: ......