Fulfill
Retrofit for Mesa
Melters
18
Part 1121938_02
2013
Nordson Corporation
PCA
(contd)
A potentiometer labeled fault limits the amount of filling time in case of
level sensor failure. t is only for overflow protection. The factory
setting is at the 12 o'clock position, sufficient in most applications.
The time can be adjusted from 5 to 115 seconds. For reference, the 9
o'clock position is 22 seconds and the 3 o'clock position is 98
seconds.
A potentiometer labeled ”AIR” is a pre‐vibrate timer for the optional
storage bin vibrator kit. The range for this potentiometer is 0 to 20
seconds. When installed, this vibrator will activate up to 20 seconds
before the fill system activates and stay on until the level sensor is
satisfied. This kit is well suited for adhesives and plant conditions
that are prone to bridging.
A dip switch labeled SW1 is preset at the factory. Position M1 should
always be OFF and position M2 should always be ON.
A terminal block labeled ”XT2”. An optional light tower may be
attached here. The functions of the light tower are
‐
Fill (Blue) - visual
‐
Fault (Red) - visual
‐
Fault (Alarm) - audible.
NOTE:
The fault outputs will engage simultaneously.
(7). Sensor (Not Shown)
NOTE:
Refer to
Appendix A, Retrofit Refill System With Nordson Level Sensor,
for updated
information.
The level sensor detects the level of adhesive in the melter tank. When the
adhesive falls below the set point, the level sensor sends a signal to the Fulfill
control box.
The sensor will require calibration when the adhesive is molten. See the
Level Sensor Adjustment and Calibration
detailed later in the manual.
Summary of Contents for Mesa Fulfill
Page 46: ...Fulfill Retrofit for Mesa Melters 42 Part 1121938_02 2013 Nordson Corporation Wiring Diagram...
Page 47: ...Fulfill Retrofit for Mesa Melters 43 Part 1121938_02 2013 Nordson Corporation Dimensions...
Page 48: ...Fulfill Retrofit for Mesa Melters 44 Part 1121938_02 2013 Nordson Corporation...
Page 64: ......
Page 65: ......
Page 66: ......