HTL encoder function (only DIN2/4 )
For the evaluation of an HTL encoder, the digital inputs DIN2 and DIN4 must be parameterised with
the following functions.
Value Function
Description
Signal
43
Track A
HTL
encoder
This function
can only be
used for digital
inputs 2 (DIN2)
and 4 (DIN4)
!
A 24V HTL encoder can be connected to
DIN 2
and
DIN 4
in order to
measure the speed. The maximum frequency at the DIN is limited to
10kHz. Accordingly, a suitable encoder (low pulse number) or
suitable mounting (slow speed) SHOULD BE USED.
The direction of counting can be changed by exchanging the
functions on the digital inputs.
Further settings are in P461, P462, P463.
Impulse
<10kHz
44
Track B
HTL
encoder
Impulse
<10kHz
Pos: 261 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterüberschrift - Fortsetzung Tabelle @ 1\mod_1331566123473_388.docx @ 18340 @ @ 1
Parameter
{factory setting}
Setting value / Description / Note
Supervisor
Parameter
set
Pos: 262 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P400-P499/Parameter P426 – Schnellhaltezeit @ 0\mod_1328000414237_388.docx @ 10020 @ @ 1
P426
Quick stop time
(Quick stop time)
P
0 ... 320.00 sec
{ 0.10 }
Setting of the stop time for the fast stop function which can be triggered either via a digital input,
the bus control, the keyboard or automatically in case of a fault.
Emergency stop time is the time for the linear frequency decrease from the set maximum
frequency (P105) to 0Hz. If an actual setpoint <100% is being used, the emergency stop time is
reduced correspondingly.
Pos: 263 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P400-P499/Parameter P427 – Schnellhalt bei Störung [SK 1x0E, SK 5xxE] @ 0\mod_1328000585707_388.docx @ 10043 @ @ 1
P427
Emergency stop on error
(Emergency stop on error)
S
0 ... 3
{ 0 }
Activation of automatic emergency stop following error
0 = OFF:
Automatic emergency stop following error is deactivated
1 = Mains supply failure:
Automatic emergency stop following mains supply failure
2 = In case of faults:
Automatic emergency stop following fault
3 = Fault or mains failure:
Automatic emergency stop in case of fault or mains failure
An emergency stop can be triggered by the errors
E2.x, E7.0, E10.x, E12.8, E12.9
and
E19.0
.
Pos: 264 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P400-P499/Parameter P428 – Automatischer Anlauf @ 0\mod_1328000652144_388.docx @ 10066 @ @ 1
P428
Automatic starting
(Automatic starting)
S
P
0 ... 1
{ 0 }
In the standard setting (P428 =
0
Off
) the inverter requires a flank to enable (signal change
from "low
high") at the relevant digital input.
In the setting
On
1
the FI reacts to a High level. This function is only possible if the FI is
controlled using the digital inputs. (see P509=0/1)
In certain cases, the FI must start up directly when the mains are switched on. For this P428 =
1
On
can be set. If the enable signal is permanently switched on, or equipped with a cable
jumper, the FI starts up immediately.
NOTE:
(P428) not "ON" if (P506) = 6,
Danger!
(See note on (P506))
Pos: 265 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P400-P499/Parameter P429 – Festfrequenz 1 @ 0\mod_1328000717565_388.docx @ 10089 @ @ 1
Summary of Contents for NORDAC PRO SK 5 E-111 CP Series
Page 1: ...EN BU 0505 SK 54xE Users Manual for Frequency Inverters...
Page 5: ...Publisher BU 0505 EN 3021 5...
Page 214: ...SK 54xE Users Manual for Frequency Inverters 214 BU 0505 EN 3021...
Page 215: ...Key word index BU 0505 EN 3021 215...
Page 216: ...SK 54xE Users Manual for Frequency Inverters 216 BU 0505 EN 3021...
Page 217: ......
Page 218: ...6075052 3021...