Error
Possible
Reason
Correction
In case of using one or several outputs: check
following systems/indicators if they are potential-
free. Two analog outputs at a time have a com-
mon ground.
Programming
Output enabled?
Check if functions have been assigned to correct
output channel.
Check output range
(0 or 4…20 mA)
Check output span
Check offset
Check output signal in I/O menu
Following
systems
Check cables and connections, overvoltage pro-
tection elements as well as input and output
clamps.
Check input range (0 or 4…20 mA) of following
system.
Check input span of following system.
Check possible offset of following system.
Real time clock
shows incorrect
time
Buffer battery
empty
Let NIVUS replace the built-in buffer battery.
Attention: replacement must be carried out only
by NIVUS or personnel authorised by NIVUS.
Otherwise the warranty will expire.
Parameter
memory shows no
parameters
Buffer battery
empty
Let NIVUS replace the built-in buffer battery.
Attention: replacement must be carried out only
by NIVUS or personnel authorised by NIVUS.
Otherwise the warranty will expire.
Summary of Contents for NFP
Page 82: ...Instruction Manual NIVUS Full Pipe page 82 NFP rev 04 23 05 2018 Approvals and certificates...
Page 83: ...Approvals and certificates NFP rev 04 23 05 2018 page 83...
Page 84: ...Instruction Manual NIVUS Full Pipe page 84 NFP rev 04 23 05 2018...
Page 85: ...Approvals and certificates NFP rev 04 23 05 2018 page 85...
Page 86: ...Instruction Manual NIVUS Full Pipe page 86 NFP rev 04 23 05 2018...
Page 87: ...Approvals and certificates NFP rev 04 23 05 2018 page 87...