39
Model
Power Level
Rear Cover Diagram
NUPS23-1000
1000 VA / 900W
FIG. 17
NUPS23-1500
1500 VA/ 1350W
FIG. 17
NUPS23-2000
2000 VA / 1800W
FIG. 18
NUPS23-3000
3000 VA / 2700W
FIG. 18
Table 13.
Product Performance
Model NUPS 23-
1000
1500
2000
3000
Rated capacity
900W/1000VA
1350W/1500VA
1800W/2000VA
2700W/3000VA
input
input
Single phase and ground
Voltage range
55±5V~145±5V (load≤60%);
60±5V~145±5V (60%<load≤70%);
70±5V~145±5V (70%<load≤80%);
80±5V~145±5V (load>80%);
Nominal
Frequency range
50/60 Hz ±0.5Hz auto sensing
46Hz-54Hz±0.5Hz@50HZ or 56Hz-64Hz±0.5Hz@60HZ
Power factor
≥0.98
Current harmonic
< 10% (100% linear load )
output
Output style
Single phase and ground
Rated voltage
100/108/110/115/120Vac
Power factor
0.9
Voltage precision
±2%
Output
Frequency
Line
mode
1、When input frequency is in the range, the output
frequency synchronized with the utility in AC mode.
2、When input frequency is out of the range, the output
frequency is (50/60 ± 0.2) Hz when in battery mode
Battery
(50/60 ± 0.2) Hz
Crest ratio
3:1
Transfer time
Mains ←→ battery = 0ms
Mains ←→ bypass < 4ms
Overload
capacity
>110%, 30s turn to bypass mode
>150%, 300ms turn to bypass mode
Efficiency
Line
mode
Full load ≥ 86%