Replacing Batteries
NOTE DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
。
The EBP can be replaced when UPS is ON, but be aware that if the utility fails at that
time , the load of the UPS may NOT be protected. If you prefer to remove input
power to change the batteries, see “UPS Turn on and Turn off”.
Replacing RT UPS and EBPS
1.
If the battery fault, the following steps are provided for modular unit to replace the new battery
pack
2.
2. Remove the front cover of the battery box.
3.
Remove the connection cables between battery box and UPS. Release the screw of the baffle of
the battery pack as the Fig.22 shows and remove the baffle from the left or right.
FIG.22
The Installation for baffle of battery pack
4.
Grasp the handle in front of the battery pack, pull it out, and remove the battery pack as fig. 23
shown.