27
more than half a second (less than 2 seconds), select
the EPO input polarity, “+P”(open circuit execute
EPO function) or “–P”(short circuit execute EPO
function)
③ Confirm the setting. After selecting EPO input
polarity, press and hold the function setting
key
for more than half a second (less than 2
seconds). Now, the setting is confirmed.
④ Exit from the setting interface. Press and hold
function setting key
for more than half a second
(less than 2 seconds), exit from the setting interface
and return to main interface.
Frequency
Converter mode
setting(7)
①Enter the setting interface. Press and hold the
function setting key
for more than 2 seconds, then
come to setting interface, Press and hold the scroll
key
for more than half a second(less than 2
seconds), select the function setting, choose output
frequency setting interface, the letters “OPF” will
flash.
② Enter the output frequency of converter mode
setting interface. Press and hold the function setting
key
for more than half a second (less than 2
seconds) , the letters “OPF” will stop flashing. The
letters below the “OPF” will flash. Press and hold
the scroll key
for more than half a second (less
than 2 seconds), select the output frequency,
“50Hz”(output fixed to 50Hz and active converter
mode) or “60Hz”(output fixed to 60Hz and active
converter mode) or “IPF”(inactive converter mode
and active normal mode)
③ Confirm the setting. After selecting converter
mode output frequency, press and hold the function
setting key
for more than half a second (less than 2
seconds). Now, the setting is confirmed.
④ Exit from the setting interface. Press and hold
function setting key
for more than half a second
(less than 2 seconds), exit from the setting interface
and return to main interface.