13
FIG.11
Removing the UPS Cable Knockout
3.
For the bottom (or only) EBP, remove the EBP cable knockout on the top of the EBP front cover.
See FIG. 11 for the location of the top EBP cable knockout.
4.
If you are installing more than one EBP, for each additional EBP remove the EBP cable knockout
on the top and bottom of the EBP front cover. See FIG. 11 for the location of the EBP cable
knockouts.
CAUTION
A small amount of arcing may occur when connecting an EBP to the UPS. This is normal and will not
harm personnel. Insert the EBP cable into the UPS battery connector quickly and firmly.
5.
Plug the EBP cable(s) into the battery connector(s) as shown in FIG. 12. Up to four EBPs may be
connected to the UPS. Connect black to black. Press the connector tightly together to ensure a
proper connection.
To connect a second EBP, unclip the EBP connector on the first EBP and pull gently to extend the
wiring to the EBP connector on the second EBP. Repeat for any additional EBPs.
6.
Verify that the EBP connections are tight and the adequate bend radius and strain relief exist for
each cable.
FIG.12
Typical EBP Installation
7.
Replace the EBP front cover.