ERROR CODES
In the event of an error, the message “errors” (see Measurement mode, appendix 5) immediately appears
regardless of which device the error is connected to.
Errors occurring during operation will be collected in the E (Error) table where the error identifier message can
be viewed.
Errors
E
01: SE300-11 : Response
02: ST300-11 : Program
03: SP300-11 : Device
“Sensor”
and
“Reply”
error message will automatically be erased from the list upon termination of the error.
Other errors entries will remain in the table until acknowledgement by pressing ESC. Thus for instance if a relay or current output set for function “Error”, it will
indicate the error even after termination of the error until the error is acknowledged as above.
E
RROR CODE
M
ESSAGE
E
RROR DESCRIPTION
C
ORRECTION
1
Init
Device does not reply after switching-on*
Check wiring of device
2
Reply
Device with normal operation does not respond **
Check wiring of device
3
Sensor
Sensor failure on the device ***
Check device (transmitter)
4 Device
Other
device
Error (See chart next page)
Check programming of device ( See relevant Install and Prog. Manual), and
measurement conditions
5 Program
Error occurred during programming of relay or current
output ****
Check programming
6
Save
Error occurred in the course of saving to memory
If this happens repeatedly, send device to the manufacturer.
7 Log
Logging does not answer or a failure may happened
during the saving process
Please check the memory card, if necessary try with another SD card.
* An active device on the list does not reply after switching-on. Possible reasons:
the system was modified before turning on (device was disconnected, the wiring was changed, etc.)
device failed to reach operation conditions during the boot process (and is not yet able to measure) thus this error message appears
(e.g. in solid applications, STD-300 transmitters may not respond until the amplification reaches operation conditions).
** A device that had been working perfectly suddenly stops responding. Possible reasons:
the device has gone wrong
broken cable
noisy HART line (See Main menu/MultiCONT config/HART test)