TOT1
Default: Invert = OFF
relay will be de-energized when TOT1 reaches value in RP1
Operation
can be
inverted by selecting Invert = ON (relay will be
energized)
t
Energised
De-energised
TOT1
20
RP1=20
Relay
RP1
Alt
(optimized pump control)
Default: Invert = OFF
More relays (max 8) can be assigned to one source (transmitter)
and they are controlled such that the switching number will be the
same for all of them.
In this case the connected relays will be energized and de-
energized one after the other irrespective of which relay’s
conditions are fulfilled.
As in the diagram, relays programmed in this manner operate in
the following sequence for:
Mode: Alt S
1 23 1 23 Energised
123 1 2 3 De-energised
Mode: Hysterisis
3 32 2 21 Energised
123 3 2 2 De-energised
t
R3
Energised
De-energised
Relay
RP1
RP2
R1
RP1
RP2
R3
RP1
RP2
R2
R1
Energised
De-energised
Relay
R2
Energised
De-energised
Relay
Energised
De-energised
1
123
1
2
3
2
1
3
23
RP1,
RP2