5. Operation
5. Operation
.26.
.27.
5.5.3.1 Battery Select
There are some options about battery modules. When some battery module is selected, pre-
settings will be imported, user doesn't need to configure the battery parameters except for
over discharge SOC and forced charge SOC.
5.5.4.1 Backup ON/OFF
This switch is to enable or disable the backup port of the inverter.
5.5.4.1 Backup Settings
Set the voltage/frequency of the backup port.
Enable or disable the voltage droop.
The OverDischg SOC can be set from 10% to 40%.
The ForceChagre SOC can be set from 5% to OverDischg SOC.
5.5.4 Backup Control
This function is used for set the backup port.
5.5.5 Storage Energy Set
It includes “Stg mode select” which defines different working logic of the hybrid inverter. There
are two options in the Stg Mode Select: Time charging and Off-grid.
Another default mode is Auto mode (Maximize the self-consumption rate) which is
not shown in the setting. Once the inverter is started, it is working in the Auto mode.
If want to switch back to Auto mode, simply turn off the other modes, then it is automatically
operating in the Auto mode, even though it is NOT shown on the screen. The user can set the
time periods, for when the inverter charges and discharges the batteries,
using Time Charging Mode.
In installations where no grid is present, it is recommended to use Off-Grid mode.
Figure 5.24 Storage energy set
Mode:
Off Grid Mode
NOTE:
Available Batteries with built-in protocol: Pylon, BYD.
Figure 5.19 Battery select
Battery Select:
PYLON
Figure 5.20 Overdischg SOC
Overdischg SOC:
029%
Figure 5.21 Backup control
Backup ON/OFF
Backup Settings
Figure 5.22 Backup ON/OFF
Set Backup:
OFF
Figure 5.23 Backup settings
Backup Voltage:
230.0V