5. Operation
5. Operation
.24.
.25.
5.5 Advanced Settings
Select Advanced Settings from the Main Menu to access the following options:
1. Select Standard 2. Grid Switches 3. Battery Control 4. Backup Control
5. Storage Energy Set 6. STD. Mode Settings 7. Software Update
8. Export Power Set 9
.
Calibrate 10. Reset Password 11. Restart HMI
5.5.1 Selecting Standard
This function is used for select the grid's reference standard.
Below is the setting range for “ User-Def”. Using this function, the limits can be changed
manually.
OV-G-V1: 240---270V
OV-G-F1: 50.2-53Hz(60.2-63Hz)
OV-G-V1-T: 0.1---9S
OV-G-F1-T: 0.1---9S
OV-G-V2: 240---300V
OV-G-F2: 50.2-53Hz(60.2-63Hz)
OV-G-V2-T: 0.1---1S
OV-G-F2-T: 0.1---9S
UN-G-V1: 170---210V
UN-G-F1: 47-49.5Hz(57-59.5Hz)
UN-G-V1-T: 0.1---9S
UN-G-F1-T: 0.1---9S
UN-G-V2: 110---210V
UN-G-F2: 47-49Hz(57-59.5Hz)
UN-G-V2-T: 0.1---1S
UN-G-F2-T: 0.1---9S
Startup-T:10---600S
Restore-T:10---600S
5.5.2 Grid Switches
This function is used for start up or stop working.
Selecting the “User-Def” menu will access to the following submenu.
5.5.3 Battery Control
This function is used for set the battery.
Figure 5.18 Battery control
→
Battery Select
NOTE:
The " User-Def" function can be only used by the service engineer and
must be allowed by the local energy supplier.
→
Grid ON
Grid OFF
Figure 5.17 Set grid ON/OFF
NOTE:
This function is for technicians use only.
NOTE:
To access to this area is for fully qualified and accredited technicians only.
Please follow 5.4 to enter password to access this menu.
Figure 5.15 Selecting standard
YES=<ENT> NO=<ESC>
Standard: G98
→
OV-G-V1: 260V
OV-G-V1-T: 1S
Figure 5.16