5. Operation
5. Operation
.28.
.29.
5.5.6 STD. Mode Settings
There are 5 setting under STD. Mode settings.
1. Working mode
2. Power Rate limit 3. Freq. Derate set 4. 10mins OV-G-V set.
5.Initial Settings
5.5.8.2 EPM ON/OFF
There are 2 settings in this menu as below:
1. ON
2. OFF
5.5.8.3 Backflow Power
This submenu is used for set allowed power that inverter can send to grid.
5.5.6.1 Enable logic interface settings
When select G98 or G99 standard to use the logic interface function, please follow below
settings to enable the DRM. DRM default setting is “OFF” , if DRM set “ON”, but the logic
interface un-connected to the switch or the switch is open, the inverter HMI
will display “Limit by
DRM” and the inverter output power will be limited to zero.
1. Select Initial Settings
2. Select DRM and set it
“ON”
5.5.7 Software Update
There are 2 settings under Software Update.
1. HMI Update
2. DSP Update
5.5.9 Calibrate
Maintenance or replacement could clear or cause a different value of total energy. This function
allows user to revise the value of total energy to the same value as before. If the monitoring
website is used the data, it will be synchronous with this setting automatically.
5.5.8 Export Power Set
Select EPM Settings from the Main Menu to access the following options:
1. Meter/CT Select
2. EPM ON/OFF
3. Backflow Power
5.5.8.1 Meter/CT Select
There are 2 settings in this menu as below:
1. CT
2. Meter
5.5.10 Reset Password
This function is used for set the new password for menu “Advanced info.” and “Advanced
information” .
Enter the right password before set new password. Press the DOWN key to move the cursor.
Press the UP key to revise the value. Press the ENTER key to execute the setting. Press the
ESC key to return to the previous menu.
Figure 5.27 Reset password
YES=<ENT> NO=<ESC>
Password: 0000
This function is applicable by maintenance personnel only, wrong
operation will prevent the inverter from working properly.
This function is applicable by maintenance personnel only, wrong
operation will prevent the inverter from working properly.
Figure 5.25 Backflow power
YES=<ENT> NO=<ESC>
P_Backflow:-0001W
Figure 5.26 Calibrate
YES=<ENT> NO=<ESC>
Energy:0000000kWh