3. -FVT/-FVC Option Setting
When equipped with -FVT/-FVC option, following setting options are enabled from function setting feature.
No.
Setting item
Description
Input range
Default
F11
Maximum analog
signal displayed
value
Set the displayed value which corresponds to
the maximum value of each analog signal.
Mode 1 ●000000● ● ●999999●
1000
● 4 ● 20 mA
● 0 ● 10 V
● 1 ●●5 V
● 0 ●●1 V
● Maximum value●20 mA
● Maximum value●10 V
● Maximum value●●5 V
● Maximum value●●1 V
Mode 2
Hour:Minute:Second
●_0:00:00● ● ●_9:59:59●
Displayed in Seconds
10:00
Displayed in Seconds
●_000:00● ● ●_999:99●
Mode 3
Hour:Minute:Second
●_0:00:00● ● ●_0:59:59●
Displayed in Seconds
10:00
Displayed in Seconds
●_000:00● ● ●_999:99●
Mode 4 ●000000● ● ●999999●
1000
F12
Minimum analog
signal displayed
value
Set the displayed value which forces the output
of the minimum value of each analog signal.
Mode 1 ●000000● ● ●999999●
1000
● 4 ● 20 mA
● 0 ● 10 V
● 1 ●●5 V
● 0 ●●1 V
● Minimum value●4 mA
● Minimum value●0 V
● Minimum value●1 V
● Minimum value●0 V
Mode 2
Hour:Minute:Second
●_0:00:00● ● ●_9:59:59●
Displayed in Seconds
10:00
Displayed in Seconds
●_000:00● ● ●_999:99●
Mode 3
Hour:Minute:Second
●_0:00:00● ● ●_0:59:59●
Displayed in Seconds
10:00
Displayed in Seconds
●_000:00● ● ●_999:99●
Mode 4 ●000000● ● ●999999●
1000
F13
Analog signal
output timing
Maximum speed when the period is zero.(10ms).
When the period is 1, analog signal output is
renewed at each display renewal cycle.
● when the frequency is above 200Hz
● _ 0_ ● (Maximum speed )/
● _ 1_ ● (In sync with display renewal)
0
(Maximum speed)
F14
Analog signal
output offset
Set the output offset value as the percentage of
the output range for each analog signal.
●__-100.0● ● ●__100.0●●
0●
● 4 ● 20 mA
● 0 ● 10 V
● 1 ●●5 V
● 0 ●●1 V
● Output range●16mA
● Output range●10V
● Output range●●4V
● Output range●●1V
● When offset is OFF ●off set F14 = 0●●
● When offset is ON ●off set F14 > 0●
● When offset is ON ●off set F14 < 0●
Condition
Analog output value
displayed value ● F11set value
Maximum value ●20mA● 10V● 5V● 1V●
F12 ● displayed value ● F11
(Maximum value/ F11)× Measured value for analog output
displayed value ● F12 set value
Minimum value ●4mA● 0V● 1V● 0V●
Condition
Analog output value
displayed value ● F11´●
Maximum value ●20mA● 10V● 5V● 1V●
F12 ● displayed value ● F11´
●
(Maximum value/ F11)×Measured value for analog
(Offset value)
displayed value ● F12 set value
Minimum value ●4mA● 0V● 1V● 0V) + (MAX ●● F14(● ))
Condition
Analog output value
displayed value ● F11´●
Maximum value ●20mA● 10V● 5V● 1V●
F12 ● displayed value ● F11´
●
(Maximum value/ F11)×Measured value for analog output-
(Offset value)
displayed value ● F12 set value
Minimum value ●4mA● 0V● 1V● 0V) - (Offset value)
● F11' is the displayed value when the analog output value, including F14(%) of the
output range, is equal to the MAX value.
Example) Assuming the output is 10V, F11= 200, F14 = 10(%), then F11'= 180,
therefore the output is 10V when the displayed value is above 180.
● The minimum value for MIN-F14(%) in the diagram above is 0mA, in the case of
current output (4 ● 20mA)
Example) Assuming the output is 10V, F11= 200, F14 = -10(%), then F11'= 220,
therefore the output is 10V when the displayed value is above 220.
● The minimum value for MIN-F14(%) in the diagram above is 0mA, in the case of current output (4 ● 20mA)