23
●
24. Option -FVT/-FVC
Model
-FVT/-FVC
Output
Current output
4 ● 20mA
Select one of these
four output options
Voltage output
0 ● 10V
1 ● 5V
0 ● 1V
Load
Output current
below 500Ω
Output voltage
above 1kΩ
Connector
●FVC)*
Meter :PCS-E36LMD
Attachment : ●Plug● PCS-E36SF● ●Cover● PCS-E36LA
(Both manufactured by HONDA TSUSHIN KOGYO CO., LTD.)
When equipped with -FVT/-FVC option, analog signal output (voltage/current) is available
according to the displayed data.
*Cables are to be connected by the user.
●
1. Specifications for -FVT/-FVC Option
●
2. Connection for -FVT/-FVC Option
●●
-FVT Option (Terminal block)
● ●
-FVC Option (Connector)
C+
C-
NC
NC
V1-
4 ● 20mA
0 ● 10V
1 ● 5V
0 ● 1V
+
+
+
+
-
-
-
-
V10+
V10-
V5+
V5-
V1+
*Select one out of these output options
11 12 13 14 15 16 17 18 19 20
Code
Pin number
Code
C+
4 ● 20mA+
1
19
C-
4 ● 20mA-
2
20
NC
3
21
NC
NC
4
22
NC
NC
5
23
NC
NC
6
24
NC
NC
7
25
NC
NC
8
26
NC
V10+
0 ● 10V+
9
27
V10-
0 ● 10V-
10
28
NC
11
29
NC
NC
12
30
NC
V5+
1 ● 5V+
13
31
V5-
1 ● 5V-
14
32
NC
15
33
NC
NC
16
34
NC
V1+
0 ● 1V+
17
35
V1-
0 ● 1V-
18
36
*1 and 2 are interconnected to each other. 9-10, 13-14, 17-18, 19-20,
27-28, 31-32, 35-36 are also interconnected respectively.
Connector numbering
(as the plug is viewed from wire connection side)
● The connector next to “1”marking is #2 terminal.
● Suggested wiring order is 1● 3● 5 ● 20● 22● 24 ● for the
ease of finding the right numbering.
● Please use extra caution in soldering, as the clearance is small.
● ● 35 36
1 2 3 4 ● 17 18
19 20 35 36
*Select one out of these output options
www.calcert.com
1.888.610.7664
0
5
10
15
20
25
30