15
Press the SET key.
The display goes to mode 4
(flowmeter mode).
0. 0
0 4 - P 0 1
- - - -
0 1
-
1. 0
-
-
0 0 0 2. 5
0 0 0 0. 0 6
- - - -
0 1
-
0 0 0 1. 0
0 0 0 0 1. 0
0 0 0 0 0. 0
0 0 0 0 0. 0
-
1. 0
-
-
1 0
-
-
1 0
-
0. 0
- -
0 0 6. 0
- -
0 0 6. 0
No.
Setting item
Description
Input range
Default setting
F1 High set point 1 value
Sets the high set point 1 value
000000 - 999999
0
F2 Low set point 1 value
Sets the high set point 1 value
000000 - 999999
0
F3 High set point 2 value
Sets the high set point 2 value
000000 - 999999
0
F4 Low set point 2 value
Sets the low set point 2 value
000000 - 999999
0
F5
Hysteresis of the high and
low set point 1 values
Sets the hysteresis of the high and low set point 1 values
0 - 99
0
F6
Judgment output timer at
startup
Sets the time when the comparator judgment is output at startup
0 - 99 sec.
0 sec.
F7 Minimum flow(display value)
Sets the revolution speed to be displayed as zero
000000 - 999999
0
F8
Frequency of the moving
average
Used when variation of the revolution speed is large and a stable
display cannot be attained
0(disabled)/1(3 times)/2(10 times)
0(disabled)
F9 Pre-arithmetic function
Promptly performs the deceleration display when the signal is lost
0(disabled)/1(enabled)
0(disabled)
* For the description of functions, refer to page 21.
Use the key to move to another digit
Use the key to change the numerical value
to “0.06”.
Use the ENT key to finish setting.
Use the key to select the decimal point,
and use the key to change its position.
• Start setting according to the setting example on the previous page.
Normal display
Parameter 1 setting
To the parameter settings
Parameter 2 setting
Parameter 3 setting
Parameter 4 setting
Parameter 5 setting
Parameter 6 setting
Parameter 7 setting
Finish setting
The main display shows “0:00”.
Press the ENT key and star t
setting parameters. (The main
d i s p l a y s h o w s t h e c u r r e n t
set numerical value of each
parameter.)
Every time you press the ● key,
the display switches to the next
parameter.
Press and hold the SHIFT +
PAR A keys for 5 seconds or
more to switch to the param-
eter setting mode.
The numerical value does not need to be
changed and you can proceed to the next
step by pressing the ENT key.
(Use the key to change the numerical
value.)
The numerical value does not need to be
changed and you can proceed to the next
step by pressing the ENT key.
(Use the key to change the numerical
value.)
The numerical value does not need to be
changed and you can proceed to the next
step by pressing the ENT key.
(Use the key to change the numerical
value.)
The numerical value does not need to be
changed and you can proceed to the next
step by pressing the ENT key.
(Use the key to change the numerical
value.)
The numerical value does not need to be
changed, and go to next step.
(Use the key to move to another digit)
(Use the key to change the numerical
value.)
Use the key to move to another digit
Use the key to change the numerical value
to “2.5”.
Use the ENT key to finish setting.
• Function setting item in mode 4 (flowmeter mode)
(3) Function (For the setting method, refer to pages 16 and 17.)
*If you enter a value outside the setting range, all the input values will blink, which indicates the setting is disabled.
●When this occurs, you cannot switch to other displays until you enter a value within the setting range.
s
s
s
s
s
s
s
s
s
s
s
s