TABLE 6 - First level functions

LED

Description

Example

L1

Automatic closure

This function performs automatic closure of the pole after the programmed pause time. Factory setting: 
20 seconds. Value programmable from 3 to 60 seconds.

L2

Reclose after photo 

This function enables the pole to remain in Opening position for the time required for transit. When the function is
active, operation depends on the parameter set in the function “Automatic closure”:

• with “Automatic closure” active, the Opening manoeuvre stops immediately after the photocells are disengaged
and the Closure manoeuvre starts after 5 seconds.

• with “Automatic closure” not active, the pole always reaches the maximum Opening position (even if the 
photocells are disengaged beforehand) and Closure starts after 5 seconds.

L3

Always close

This function is useful in the event of a power failure, even brief. In fact if this function is active (ON), when power

is 

restored, the control unit detects the pole as open and starts Closure. For reasons of safety the Closure manoeuvre
is preceded by a 3-second pre-flashing interval.

L4

Stand by

This function allows consumptions to be reduced. If active, 1 minute after the end of the manoeuvre, the control 
unit turns off the TX of the Bluebus photocells and all the LEDS, excluding the Bluebus LED which flashes more 
slowly. When the control unit receives a command normal operation is restored. 

For the use of the barrier with

the Solemyo system it is necessary to activate an even deeper “Stand by” mode, the “Stand by all”. 

This operation is performed using the Oview programmer.

L5

Long/short deceleration

This function enables the user to double the space for starting deceleration, both in Opening and Closing. If the 
function is deactivated, deceleration is short.

L6

Automatic start-up

This parameter, if active (ON), lets you activate the start-up (starting at maximum speed) until the pole is made to

move. The default value is “OFF”.

L7

Modo Slave

By activating this function the barrier becomes “Slave”: it is possible to synchronize the operation of 2 
counterposed barriers where one works as Master and the other as Slave; for more information see
paragraph 7.6 - Master-Slave Mode.

L8

Direction of motor rotation

This parameter enables inversion of the direction of motor rotation to enable barrier installation  on the right; the 
factory setting is “OFF” (standard motor rotation – pole closure on left).

Important – If the function is activated, the Opening and Closing positions must be memorised again 
(Paragraph 4.5)

.

EN

10

– English

The control unit has 3 keys 

OPEN

(

), 

STOP

(

Set

), 

CLOSE

(

) (

Fig. 49

) that

can be used both for controlling the unit during testing and for programming
the available functions.
The programmable functions available are divided into 2 levels and their relative

operating status is displayed by
means of the 8 LEDs (

L1

... 

L8

)

on the control unit.

LED SIGNALS:
• Led lit

= function active;

• Led off

= function not active.

PROGRAMMING KEYS:
• OPEN

(

): the “OPEN” key

enables control of pole opening
or can be used, during program-
ming, to move the programming
point up.

• STOP

(

Set

): the “STOP” key enables the user to stop the manoeuvre; if

pressed for more than 5 seconds, it enables entry to programming mode.

• CLOSE

(

): the “CLOSE” key enables control of pole closing or can be used,

during programming, to move the programming point down.

IMPORTANT! – During a manoeuvre (open or close) all 3 keys (

Set,

) work as STOP; causing the maneuver underway to stop or the

reverse of the maneuver.

6.1 - Level one programming (ON-OFF functions)

All the level 1 functions (

Table 6

) are set by default to “

OFF

” and may be mod-

ified at any time as explained in 

Table 7

. The parameters can be set on a scale

from 1 to 8. To check the value corresponding to each LED see 

Table 6

.

IMPORTANT

– In the programming procedure, the maximum time interval that

can elapse between activation of one key and the next is 10 seconds. When
this time elapses, the procedure terminates automatically, memorising the
modifications made up until then.

CONTROL UNIT PROGRAMMING

6

IMPORTANT

– In the programming procedure, the maximum time interval that

can elapse between activation of one key and the next is 10 seconds. When
this time elapses, the procedure terminates automatically, memorising the
modifications made up until then.

6.2 - Level two programming (adjustable parameters)

All level 2 parameters are set by default (

Table 8

) and may be modified at any

time as explained in 

Table 9

.

The parameters can be set on a scale from 1 to 8. To check the value corre-
sponding to each LED see 

Table 8

.

Open

Stop

Set

Close

L1

Close

Open

PP

Stop

Bluebus

Light

2

L2

L3

L4

L5

L6

L7

L8

BusT4

Open

Stop

Set

Close

TABLE 7 - Programming procedure (first level functions)

01.

Press and hold down the “

Set

” key for approx. 3 seconds;

02.

Release the key when LED 

L1

starts flashing;

03.

Press keys “

” or “

” to move from the flashing led to the led associated with the function to be modified;

04.

Press “

Set

” to change the status of the function:

(short flash = OFF; long flash = ON)

05.

Wait 10 seconds (maximum time) to exit the programming mode.

Note 

– During this procedure, points 03 and 04 need to be repeated when programming other functions to “ON” or “OFF” during the phase itself.

SET

SET

SET

L1

or

3 s

10 s

Summary of Contents for M3BAR

Page 1: ...ctions et avertissements pour l installation et l utilisation ES Instrucciones y advertencias para la instalaci n y el uso DE Installierungs und Gebrauchsanleitungen und Hinweise PL Instrukcje i ostrz...

Page 2: ......

Page 3: ...ngs On the power line to the system install a device for disconnection from the power mains with a gap between contacts that assures complete discon nection in the conditions of overvoltage category I...

Page 4: ...e S p a product catalogue The electromagnetic compatibility may not be guaranteed if the product is used in configurations or with other products that have not been foreseen the use of the product is...

Page 5: ...riers for residential and indus trial use they control the opening and closing of a road transit point with widths from 3 to 8 metres IMPORTANT All uses other than the intended use described and use i...

Page 6: ...aracteristics of electrical cables 3 3 1 Modifying the factory settings of the Closure manoeuvre If Closure to the right is required proceed as follows MBAR Version 01 Remove the cover fig 4 02 Loosen...

Page 7: ...ncy must be checked and ensure that the 4 anchoring points can resist a load of at least 1000 Kg For fixture use 12 MA screws 3 5 Pole installation 3 5 1 Pole support assembly 01 Insert the two plugs...

Page 8: ...fig 24 03 Insert the universal joint in the free ends of the two poles Take care in cor rectly directing the joint since the heads of the screws must be on the same part of the holes on the poles fig...

Page 9: ...output In the factory it is configured for operation with Pole Open Indicator 24 V 10 W BLUEBUS this terminal enables the connection of compatible devices all are connected in parallel with just two...

Page 10: ...rom the power mains and insert the receiver as shown in fig 42 Table 5 shows the actions performed by the control unit according to the out puts activated or the commands sent from the radio receiver...

Page 11: ...ing the optic axis joining the two photocells by means of a cylin der diameter 5 cm length 30 cm Fig C pass the cylinder first close to the TX photocell then close to the RX and lastly at the centre b...

Page 12: ...n Paragraph 4 5 EN 10 English The control unit has 3 keys OPEN STOP Set CLOSE Fig 49 that can be used both for controlling the unit during testing and for programming the available functions The progr...

Page 13: ...the type of voltage of the selected programming level 1LIGHT Output WARNINGS Do not set an excessively high value for the motor force as this may impair operation of the safety system or damage the p...

Page 14: ...he Set key for approx 3 seconds 02 Release the key when LED L1 starts flashing 03 Press the key or to move from the LED that is flashing to LED L4 LIGHT output input LED 04 Press and hold the Set key...

Page 15: ...ction opens FA1 and opens FA2 can be connected to the Bluebus input it is necessary to cut the A jumper at the rear of TX and RX cards When these photocells intervene the control unit commands an open...

Page 16: ...olution Off All OK CLOSE input not active On CLOSE input activation Normal if the device connected to the CLOSE input is active FC1 limit switch LED Cause Solution Off Limit switch activation If the p...

Page 17: ...n During normal operation indicates Stand BY active Flashes Programming of functions in progress If this flashes together with L3 this indicates that the device learning phase of the opening and closi...

Page 18: ...Loop activation time is the time t linked to the operating modes described in Table 16 Loop frequency display signals the fluctuation frequency of the loop selected in Hz 7 5 2 Installation WARNINGS...

Page 19: ...maximum temperature admitted for the isola tion of the cable otherwise a loss in isolation towards the earth may occur TABLE 15 Function Values Default Loop 1 sensitivity 10 100 90 Loop 2 sensitivity...

Page 20: ...it is possible to carry out the following connections its own flashing light Flash its own Pole Open Indicator S C A pole lights its own sensitive edge Stop its own command device P P which commands t...

Page 21: ...he event of illegal dis posal of this product The manoeuvre is performed but shortly afterwards the pole blocks or performs a brief inversion the selected force value may be too low to enable the move...

Page 22: ...output for signal indicator 24V max 10W Output for flashing light with optional accessories XBA7 LED flashing light or XBA8 LED traffic light traffic light on cover BLUEBUS output 1 output with maxim...

Page 23: ...cil of 21 December 1988 regarding the approximation of legislation regulations and administration of Member States concerning construction products according to the following harmonised standards EN 1...

Page 24: ...02 Radio spectrum art 3 2 EN 300 330 2 V1 5 1 2010 In accordance with directive 1999 5 CE annex V the product is classified as class 1 and marked DIRECTIVE 2004 108 EC OF THE EUROPEAN PARLIAMENT AND C...

Page 25: ...sh es and the manoeuvre is not started the number of flashes depends on the reason for which the manoeuvre does not start In this case the user must press and hold the command within three seconds Aft...

Page 26: ......

Page 27: ...he test procedure 10 Check protection against the risk of lifting on automations with vertical movement it must be ensured that there is no risk of lifting This test can be performed as follows hang a...

Page 28: ...lish Date Description of operation describe checks adjustments repairs modifications etc Signature of technician Signature of owner That all phases as envisaged in the maintenance schedule have been p...

Page 29: ...mm 464 5 mm 400 mm 1219 5 mm 900 mm M3BAR M5BAR M7BAR L Bar 298 5 mm 464 5 mm 500 mm 1219 5 mm 900 mm EN with joint IT con giunto FR avec raccord ES con uni n DE mit Gelenkverbindung PL ze z czk NL m...

Page 30: ...II 4 3 b a c d g h f e c a b...

Page 31: ...III 5 6 MBAR a c d b...

Page 32: ...IV 90 8 9 MBAR a b c a b 7 a b...

Page 33: ...V 180 10 11 LBAR c a a b...

Page 34: ...VI 13 14 12 LBAR c a b...

Page 35: ...VII 15 16 18 17...

Page 36: ...VIII 19 20 21 23 22...

Page 37: ...IX 24 26 25 28 1 cm 27 29...

Page 38: ...X 33 34 30 31 32 c a b c a b...

Page 39: ...XI 35 36 37 45 38 a b a b c...

Page 40: ...C NO NO C C MOTB MOFB OPEN CLOSE TX RX 24V 4W LIGHT FLASH SCA BLUEBUS STOP OPEN CLOSE P P LIGHT FLASH SCA BLUEBUS STOP OPEN CLOSE P P LOOP2 LOOP1 41 IN 1 IN 2 IN 3 LOOP 2 MASTER SLAVE LOOP 1 OUT 3 OUT...

Page 41: ...XIII 42 43 44 STOP 45 46 LIGHT 47...

Page 42: ...XIV 48 49 50 a b c...

Page 43: ...XV 51 52 a b...

Page 44: ...XVI 53 a b c d e f g...

Page 45: ...FLASH SCA MOTB OPEN CLOSE TX RX BLUEBUS STOP OPEN CLOSE P P 24V 4W BUS T4 M S LOOP2 LOOP1 LIGHT FLASH SCA BLUEBUS STOP OPEN CLOSE P P 24V 4W BUS T4 M S LOOP2 LOOP1 NC NC NO NO C C NC NC NO NO C C 54 M...

Page 46: ...XVIII F1 F1 F2 F2 55...

Page 47: ......

Page 48: ...ISTML BARR01 4865_07 10 2011 www niceforyou com Nice SpA Oderzo TV Italia info niceforyou com...

Reviews: