background image

DPRO924

Nice

Control unit

EN -

 Instructions and warnings for installation and use

Summary of Contents for DPRO924

Page 1: ...DPRO924 Nice Control unit EN Instructions and warnings for installation and use...

Page 2: ...C A D F E B 9 6 5 8 2 3 8 4 4 7 1 2 1 210 125 310 125 310 I...

Page 3: ...3 A B 4 A B C 6 1 2 1 2 FUSE FUSE OXI New Generetion OXI SMXI II...

Page 4: ...tal deletion of the control unit s memory 6 4 3 Learning about the safety devices and DIP SWITCH programming 6 4 4 Learning about the Opening and Closing positions with an incremental encoder 6 4 5 Op...

Page 5: ...product as described in this instruction manual and for certain types of use e g excluding use solely for vehicles may cause the product to fall within the scope of Regulation No 305 2011 and its har...

Page 6: ...he ducting for routing the electrical cables and for the cable entry point into the control unit housing be aware that due to possible deposits of water in the junction wells the connection ducts migh...

Page 7: ...unit 1 24V motor 2 24V motor 3 motor Limit Switch function unavailable Connector for the electromechanical limit switch connection Common limit switch common Open input of maximum opening limit switch...

Page 8: ...stance output During the recognition phase the control unit recognises the type of device con nected and causes a STOP whenever any variation in the recognised status occurs Multiple devices even of d...

Page 9: ...ed system in a thorough and rapid manner You can connect Oview to the control unit via the IBT4N interface using a bus cable with 4 wires inside To access the BusT4 connector you need to open the cont...

Page 10: ...door Opening and Closing positions must be carried out one after the other and without interruptions They cannot be performed at different times CAUTION Procedure for motors with incremental encoders...

Page 11: ...y to set the dip switches to OFF TABLE 3 DIP SWITCH A DIP1 DIP2 DIP3 DIP4 Function OFF OFF OFF OFF Hold to run movement ON X OFF OFF Acquisition of positions and status of the ALT input OFF ON OFF OFF...

Page 12: ...10 years This must include at least an assembly drawing of the automated system a wiring diagram an analysis of hazards and solutions adopted a manufacturer s declaration of conformity of all the devi...

Page 13: ...Connecting photocells in Phototest mode The Phototest function increases the reliability of the safety devices allowing reaching category II in compliance with the EN 13849 1 standard set of the contr...

Page 14: ...e CAUTION The electrical connection of the buffer battery to the control unit must be done only after completing all the installation and programming phases since the battery is an emergency supply 6...

Page 15: ...shing light the diagnostics signals continue for two sequences of flashes e g 3 flashes short pause 3 flashes long pause repeated twice Configured with the Oview programmer as Flashing Light 1 TABLE 7...

Page 16: ...iew OUT3 output With clean contact relay programmable with Oview Aerial input 52ohm for RG58 type cable or similar for OXI New Generetion use the aerial connector on the receiver STOP input For contac...

Page 17: ...n the product conforms to the following directive in accordance with the provisions applicable to partly completed machinery Directive 2006 42 EC OF THE EUROPEAN PARLIAMENT AND COUNCIL of May 17 2006...

Page 18: ...www niceforyou com Nice SpA Via Callalta 1 31046 Oderzo TV Italy info niceforyou com IS0662A00MM_31 07 2018...

Reviews: